Yes. From the National Electrical Code: 352.10 Uses Permitted.

Does Romex need to be in conduit in an unfinished basement?

NM cable used on a wall of an unfinished basement shall be permitted to be installed in a listed conduit or tubing. So basically if the cable is on the ceiling, it does not require conduit. If the cable is run along walls, it requires some form of protection.

Can PVC electrical conduit be exposed?





Exposed — PVC conduit is permitted to be used for exposed work. PVC conduit used in an area subject to physical damage must be identified for the application [Sec. 352.10(F)]. Schedule 40 PVC conduit is permitted for exposed locations where not subject to physical damage.

Can you use PVC conduit in walls?

Some code-compliant PVC fittings can be used with ENT inside walls, floors, some ceilings or encased in concrete. Outdoor flexible nonmetallic tubing is strong, watertight, non-corrosive and weighs less. Metal or plastic boxes can be used with nonmetallic conduit. Always run a ground wire when using PVC conduit.

Where is PVC conduit allowed?

PVC conduit shall be permitted in portions of dairies, laundries, canneries, or other wet locations, and in locations where walls are frequently washed, the entire conduit system, including boxes and fittings used therewith, shall be installed and equipped so as to prevent water from entering the conduit.

Can I use PVC conduit in basement?

Yes. From the National Electrical Code: 352.10 Uses Permitted.

Is PVC conduit OK indoors?





According to Art. 352 of the NEC (see 2008 NEC Outlaws Some Nonmetallic Materials below), PVC conduit can be concealed within walls, floors, or ceilings; directly buried; or embedded in concrete in buildings of any height.

Can Schedule 40 PVC be used indoors?

Indoor Applications

PVC Schedule 40 is approved to be used indoors. It can be used behind wall or on the surface of the wall (provided it’s not subject to physical damage).

Can I run conduit indoors?

Conduits can also be highly beneficial when used indoors for exposed wires in areas such as attics and basements.

Can non metallic conduit be used indoors?



Liquidtight Flexible Nonmetallic Conduit (LFNC)

LFNC is a versatile option, approved for various indoor and outdoor applications. Usage is not allowed where it will be exposed to damage, in hazardous locations, or if temperatures exceed conduit ratings.

Does Romex need conduit?

Code and common sense both dictate that Romex shouldn’t be left exposed but must run through conduits. If you are running it through the basement or attic (or both), the wire must past through studs or be secured on top of joists or trusses.

Is PVC conduit glued?



PVC Cement

The “glue” used to join rigid PVC conduit and fittings is officially called PVC solvent cement. It comes in a small metal can with a twist-off cap, and is the same material used to join PVC plastic plumbing pipes and fittings.

Is PVC conduit waterproof?

Flexible PVC Conduit

Flexible conduit offers excellent protection from moisture due to its ingrained mechanical properties. Yet, the flexible units are best used in dry areas. The flexible conduit fittings are not as watertight as fittings for rigid PVC conduit.

What is the difference between white and GREY PVC?



There are two common types of PVC pipe – schedule 40 PVC and schedule 80 PVC. Schedule 40 PVC is usually white in color and schedule 80 is usually a dark gray (they can also be found in other colors). Their most important difference, though, is in their design. Schedule 80 pipe is designed with a thicker wall.

How often does PVC conduit need to be supported?

PVC must be supported every 3 ft. for trade sizes ½ inch through 1 inch. The support distance increases as the conduit size gets larger. For example, 2 inch PVC conduit can be supported every 5 ft; 6 inch PVC conduit can be supported every 8 ft.