Romex needs to be stapled to studs during rough framing so it doesn’t get damaged by hanging drywall. Once the walls and trim are up, if romex needs to be run through a wall cavity, it does not require fastening.

Does Romex need to be stapled to studs?


Quote from Youtube video: It actually says under securing and supporting non-metallic sheath cable shall be supported and secured by staples cable ties listed and identified for securement.

Does Romex need to be stapled in wall?





It’s code to staple them during new construction. But it’s also acceptable to leave them loose if you’re fishing wires through an existing finished wall in a remodel. Of course, in both cases they should also be anchored to the box.

Do you have to staple wires to studs?

Attaching Cables to Studding



In the codebook, section 334.30 states that flat cables must be stapled on the flat side of the cable, not on the edge. This provides a tight wire connection to the stud and prevents any damage to the wire sheathing.

Can you run Romex behind wall?

Quote from the video:
Quote from Youtube video: Running electrical wires behind your walls is a great way to add an additional outlet or switch. Right where you need it.

How often should you staple electrical wires?

Article 336-18 stated that cable must be secured in place at intervals not exceeding 4.5 feet (1.37 m) and within 12 inches (305 mm) from every cabinet, box, or fitting.

How often do you strap Romex?





Runs of NM cable must be supported at least every 54 inches. 1 They also must be secured within 12 inches of an electrical box that includes a cable clamp or within eight inches of a box or enclosure without a cable clamp.

Can electrical wire be run behind studs?

Re: Running and strapping wires behind studs



If you have a gap between the studs and the walls, you could just as well not drill any holes. Just staple the cable to the face of the studs, facing the wall.

How do you run Romex through walls?

Quote from the video:
Quote from Youtube video: Or an anchor before the wire has to go through the wall. So you would actually have to loop the wire up and back down in order to have that room to staple it and then get to go through the hole.

Is it legal to run Romex in conduit?

No, you can not run your Romex wiring in conduits. What you’re looking at in the code book is referring to THHN and other wiring, that while insulated with a single coat is not insulated with a second covering and bound to 2 or 3 other wires.

Can Romex be exposed in garage?



Exposed NM, NMC and NMS cable are allowed to be run in “one- and two-family dwellings, their attached or detached garages, and their storage buildings” by the National Electrical Code (NEC 334.10 and 334.15).

Where is Romex not allowed?

To give you an overview of what the National Electrical Code (NEC) regulations state, Romex wire shouldn’t be left exposed anywhere in the house, be it the basement, attic, or the home itself. In other words, the installation above is not compliant with the relevant codes.

How far can you run Romex?

As an example, for a 120-volt circuit, you can run up to 50 feet of 14 AWG cable without exceeding 3 percent voltage drop.



For 240-volt circuits:

14 AWG 100 feet
12 AWG 120 feet
10 AWG 128 feet
8 AWG 152 feet
6 AWG 188 feet



How far can you run 12 gauge wire on a 15 amp circuit?

You can run a 12 gauge wire up to 70 feet on a 15 amp circuit. That number drops to 50 feet if you run 12 gauge wire on a 20 amp circuit.

How far can you run 10 gauge wire on a 30 amp breaker?

How far can you run 10 gauge wire for 30 amps? 10-gauge wire is usually used for short 30 amp runs. If you plan on going over 150 feet, 8-gauge wire or thicker will be needed.

Can you bury regular Romex?

Romex cannot be used in the situation you describe as buried conduit is considered a wet location. You must use conductors such as THWN. Also, minimum burial depth for conduit (PVC I assume) is 18″, unless you run rigid or IMC, in which case you can go a minimum of 6″.

Can Romex be buried without conduit?



According to the National Electric Code, regular romex wire must be housed in conduit if run outdoors. However, UF rated wire can be run without conduit.

What is code for buried electrical wires?

Low-voltage (no more than 30 volts) wiring must be buried at least 6 inches deep. Buried wiring runs that transition from underground to above ground must be protected in conduit from the required cover depth or 18 inches to its termination point above ground, or at least 8 feet above grade.