In the 2020 NEC, this was cleared up by requiring a wire type equipment grounding conductor to be installed in outdoor portions of metallic raceway systems that use “compression-type” fittings. This will apply to all EMT, and any IMC or RMC that has been cut and is coupled or connected with a compression fitting.

Can I use EMT as a ground?

Rigid metal conduit (RMC), intermediate metal conduit (IMC) and electrical metallic tubing (EMT) are permitted per 250.118(2), (3) and (4) respectively as an Equipment Grounding Conductor. RMC, IMC and EMT are widely used in secondary power distribution systems, indoors and outdoors.

How is EMT grounded?





Metallic conduit shall be grounded at both end points by bonding to a grounding conductor, a grounded metal enclosure, or to a grounded metal cable tray. This may be accomplished:  with listed or marked grounding clamps and conductors connected externally to the conduit.

Can flex conduit be used as a ground?

Flexible metal conduit shall be permitted as an equipment grounding conductor where all of the following conditions are met: The conduit is terminated in listed fittings. The circuit conductors contained in the conduit are protected by overcurrent devices rated at 20 amperes or less.

Does ground wire count in conduit fill?

Moderator. If the EGC is in the pipe it counts as fill.

Where can EMT not be used?

Aluminum EMT cannot be directly embedded in concrete containing soluble chlorides such as calcium chloride, unwashed beach sand, sea water or coral-bearing aggregates.

How do I ground my EMT to box?





Quote from the video:
Quote from Youtube video: Friend has run a white and a black wire to the box which is perfect so now all he has to do is connect the green ground wire from the black power cord to the metal. Box you screw in that 10 32 screw.

How do you know if conduit is grounded?

Quote from the video:
Quote from Youtube video: If you have a metal box without a ground wire. And you want to know whether the box is grounded you can test it with an electrical tester.

What is permitted to serve as an equipment grounding conductor?

The equipment grounding conductor run with or enclosing the circuit conductors shall be one or more or a combination of the following: A copper, aluminum, or copper-clad aluminum conductor. This conductor shall be solid or stranded; insulated, covered, or bare; and in the form of a wire or a busbar of any shape.

Does ground wire in conduit need to be insulated?

Senior Member. Re: Bare Ground in Conduit? All conductors are required to be insulated per section 310.2(A), however the exception states bare conductors are allowed where permitted by other sections of the code, such as 250.119 which states egc can be bare, covered, or insulated.

What is the NEC code for conduit fill?



The NEC index cross-references “conduit fill” as conductor fill. The basic NEC reference is 300.17. The NEC does not provide a specific fill number, here. It merely says the number and size of conductors can’t be more than will permit heat dissipation and the ready withdrawal of conductors without damaging them.

Can two circuits share a ground?

The code requires each branch circuit to have an equipment ground (either a wire, or conduit, or cable tray as in 250.120A), they can be shared when they are in the same raceway. If all the 20A circuits are in one raceway then you just need one ground.

Does neutral count in conduit fill?

Yes you include both the neutral and ground wire in your conduit fill.

Where is EMT permitted to be used?



The use of EMT shall be permitted for both exposed and concealed work for the following: In concrete, in direct contact with the earth or in areas subject to severe corrosive influences where installed in accordance with 358.10(B) In dry, damp, and wet locations.

Is EMT good for outdoor use?

Electrical metallic tubing (EMT): Lightweight and easy to install. Intermediate metallic conduit (IMC): Has a thicker, galvanized wall, making it suitable for outdoor applications.

What can EMT be used for?

An EMT, also known as an EMT-Basic, cares for patients at the scene of an incident and while taking patients by ambulance to a hospital. An EMT has the skills to assess a patient’s condition and to manage respiratory, cardiac, and trauma emergencies.

Can EMT be used in concrete?

Electrical metallic tubing (EMT), elbows, couplings, and fittings can be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable for the condition [358.10(B)].

Is EMT permitted to be installed in cinder fill?



N (C) Cinder Fill.



Galvanized steel and stainless steel EMT shall be permitted to be installed in cinder concrete or cinder fill where subject to permanent moisture when protected on all sides by a layer of noncinder concrete at least 50 mm (2 in.) thick or when the tubing is installed at least 450 mm (18 in.)

Can EMT be used to support a box?

EMT must be secured at least every 10 ft. and within 3 ft. of every outlet box, junction box, device box, cabinet, conduit body, or other termination. An exception allows EMT to be fastened up to 5 ft.

Is EMT identified as a means of support?

Common raceways, like RMC, EMT, and PVC are not identified as a means of support for other raceways.

Can you use conduit as a support?

Besides rigid metal and intermediate metal conduit, rigid nonmetallic conduit and EMT are permitted as means of support. Using rigid nonmetallic conduit or EMT as support is only permitted if the raceway’s trade size matches, or exceeds, the conduit body’s trade size.