How big of a subpanel can I install off a 100 amp service?

First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A. You can for example add a 60A breaker to your existing panel and protect the new subpanel with a 100A rating.

What size wire do I need to run 100 amp service?





For 100 AMP service, you’ll need a #4 AWG copper wire or #2 AWG aluminum or copper-clad wire. Make sure to limit your voltage drop to 3% regardless of distance.

Can you run a 100 amp sub panel off of a 200 amp main panel?

Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn’t overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, …

What size wire do I need to run 100 amp Service 150 feet?

#00 AWG wire

Wire Size For 100 Amp Sub Panel 150 Feet Away



100 amp service 150 feet away from the sub panel requires #00 AWG wire (also known as 2/0 AWG wire). This wire has a median ampacity of 175 amps; more than enough than the required minimum 162.5 ampacity. We hope all of this helps.

How many circuits can you have on a 100 amp service?





Typical 100-amp panels have 20 circuits, meaning they can handle 20 full-sized breakers. 20/24 panels can hold 16 full-sized and 4 twin breakers (24 circuits in total). The number of breakers can max out to 30-42, too, depending on the design of your 100-amp pane.

Can you feed a 100 amp sub panel with a 60 amp breaker?

You can feed a 100 Amp panel with a 60 Amp breaker. Keep in mind that the sub panel needs to be rated above the breaker size.

What wire size do I need to go 100 feet for a 100 amp service to a workshop?

For a 100 ampere circuit, the conductors will likely be required to be 3 AWG copper or 1 AWG aluminum.

What size ground wire do I need for a 100 amp subpanel?

You are correct that for a 100A feeder, the associated ground wire needs to be an 8AWG copper or 6AWG aluminum wire.

How do you wire a 100 amp sub panel?



Quote from the video:
Quote from Youtube video: Type of wire if you're using six gauge or smaller wire. You can actually get multiple colors and you will have to get the correct colors.

Does a subpanel need a separate ground rod?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building. And yes, a sub panel in the same building as the main does not need a ground rod – only the ground wire.

Do I need a main breaker in a sub panel?

A main breaker on a sub-panel is not necessary because this is in the same building (if you are in a different building then NEC 225.31, 225.32, 225.33 apply). That said, having a main breaker in the sub-panel is also acceptable. For whatever reason (economy of scale, I guess) “main” panels are often sold cheaper.

What is the 6 breaker rule?



The “six breaker throw rule” was a requirement in the National Electrical Code that a service must have have a main disconnect that shuts off all power and it cannot take more than six switch throws to do it, and the main disconnect(s) also must be clearly marked, as in the photo above.

Can you feed a 100 amp sub panel with a 50 amp breaker?

Just wire it up. There is no problem using a sub panel that can take more current than you will ever feed it. Points to note: The cable to your hot tub will be rated for 50A (not 100A); therefore you must not upgrade the breaker in your main panel to 100A.

Why do you not bond a sub panel?

Corrosion can happen because of improper subpanel bonding as well. This is because the excessive electrical currents (coming from the hot, neutral, and ground wires) can accelerate the rate at which metal pipes or buildings start to erode.

Why does a subpanel need 4 wires?

The neutral and ground are not bonded in the subpanel. In this setup if a hot wire coming in contact with the non-current carrying parts of the electrical system, (outlet covers, panel covers etc), the 4th ground conductor will provide a low resistance patch back to the source tripping a breaker.

Why do you separate the ground and neutral in a sub panel?



With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!