Does a detached garage sub panel need a ground rod?

A detached building with a subpanel needs its own ground rod, regardless of if there are three wires or four wires feeding it. The earth is a very poor conductor.

Does a subpanel in same building need a ground rod?





Answer: No. You’d need at least one grounding electrode, or ground rod, for every sub-panel in a detached building. Whether you need two or not is determined by the soil and local regulations. So, check your local code requirements.

Does a sub panel need a separate ground?

The biggest difference between a subpanel and a main panel is that the ground and neutral buses on a subpanel have to be separated. Most panels come with a bar joining the two, which is easily removed. Code requires subpanels to have a ground connection that’s independent of the main panel’s.

How do you ground a subpanel?

Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

Does a subpanel need to be grounded to the main panel?

The neutral and ground MUST NOT be bonded at a sub-panel. They should only be bonded at the main service panel. If you bond them anywhere other than the main service, the neutral return current now has multiple paths, including though your ground wire.

How far can a ground rod be from panel?





The NEC requires all driven rods to be a minimum eight feet in the earth and for multiple connected rods a minimum spacing of six feet between rods. The width of the rod has little effect on reducing impedance to earth, however, the depth of the rod and spacing for multiple rods have a significant effect.

How many ground rods do you need for a sub panel?

ALL sub-panels in detached buildings require at least one, and sometimes two, grounding electrodes, aka ground rods. Whether or not you need two depends upon the soil conditions and the LOCAL code requirements.

Why are neutrals and grounds separated in a subpanel?

With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!

How many ground rods are required for a 200 amp service?

#4 grounding



for 200 Amp services, a #4 grounding electrode conductor (ground wire) is required.

Can I use rebar as a grounding rod?

Rebar used as a grounding rod is subject to corrosion so requires specialized encasing and enough contact with the ground to be effective. Section 250.68(C) of the NEC says rebar may extend from the concrete foundation of a building in an accessible location that is not subject to corrosion.

What is the minimum depth for a ground rod?

The only legal ground rod must be installed a minimum of 8-foot in the ground.