Grounding electrical sub panel in separate structure

  1. Replace with 4-wire feeder and separate the G and N (which would be code for a new install)
  2. Put a GFCI on the feed line (at the house panel?) and split G & N.
  3. Install a transformer to make it a separated service (and bond G N)

Does a subpanel need to be grounded separately?

An insulated neutral must also be separate from the ground bar at the subpanel and if installed in a separate building must have it’s own ground electrode with a solid #6 copper wire attached from electrode to the ground bar. The main service panel ground bar must be bonded and the subpanel unbonded.

Does a subpanel in a separate building need a ground rod?





And the ground is required to provide fault safely for the run from the main to the sub panel, so skipping that is wrong, too. Additionally grounding the sub panel is required since it’s a separate building.

How do you ground a separate building?

The grounding electrode system at the remote building or structure must be bonded to the separate building or structure disconnect. An equipment grounding conductor (bond wire) run with the feeder supply conductors to the separate building or structure must terminate to the separate building or structure disconnect.

Why do you not ground a subpanel?

So, why do you separate the ground and neutral in a subpanel? Because when we bond them together, it gives your neutral wire (the one carrying electrical currents BACK to the source) multiple pathways. That’s how the chassis of some equipment will become energized.

Can a subpanel have its own ground?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building.

Does a subpanel need to be bonded?





Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

How do you install a subpanel in a detached building?

5 Steps of Running a Subpanel to a Detached Garage

  1. Step 1: First and Foremost. Ensure that you cut your power before beginning. …
  2. Step 2: Prepare For Your Garage Subpanel. …
  3. Step 3: Install your Backer. …
  4. Step 4: Connect Your Wire to Subpanel. …
  5. Step 5: Main Panel.


Does a 60 amp sub panel need a ground rod?

In the same building or attached building no ground rod is required just hot hot neutral ground, with ground and neutral being isolated from each other in the sub panel.

How many grounding rods do I need for a sub panel?



Two hots (ungrounded conductor), one neutral, one ground (equipment grounding conductor) in 1″ pvc. Ground rod at the shed. Simple, that’s how you do it.

How do I add a ground bar to a sub panel?


Quote from Youtube video: On the left side of this homeline load center you will see a ground symbol also you'll see a hole for a screw. And two nubs which can be used to install a ground bar.

Can ground and neutral be on same bar in subpanel?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Can ground and neutral be on same bus bar?



If the main service panel happens to be the same place that the grounded (neutral) conductor is bonded to the grounding electrode, then there is no problem mixing grounds and neutrals on the same bus bar (as long as there is an appropriate number of conductors terminated under each lug).

Can neutral and ground be tied together?

No, the neutral and ground should never be wired together. This is wrong, and potentially dangerous. When you plug in something in the outlet, the neutral will be live, as it closes the circuit. If the ground is wired to the neutral, the ground of the applicance will also be live.

Does a 240v sub panel need a neutral?

A 240v only panel has no need for a neutral, I have panels in a industrial facility with no neutral, but for residential my jurisdiction requires a 4 wire feed or 3 with conduit as a ground even for all 240v loads.

How do you separate neutral and ground in main panel?

Quote from the video:
Quote from Youtube video: And we connect these neutrals and grounds with this green screw or with a jumper in between as current flows back on the neutral.