How do you separate a neutral subpanel from a ground?

Quote from the video:
Quote from Youtube video: Um is made and the service first point of disconnect is and at that point the neutrals and grounds must be bonded together to the neutral utility to the grounding electrode.

What happens if you bond neutral and ground in subpanel?





With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!

Do grounds and neutrals need to be separated in a sub panel?

The National Electrical Code (NEC) requirement for separated neutrals and grounding wires in a subpanel and separate neutral and grounding conductors back to the main panel, when both panels are in the same building, dates to the 1999 revision.

Why do you not bond the neutral in a sub panel?

So, why do you separate the ground and neutral in a subpanel? Because when we bond them together, it gives your neutral wire (the one carrying electrical currents BACK to the source) multiple pathways. That’s how the chassis of some equipment will become energized.

How do you isolate a neutral subpanel?

An insulated neutral must also be separate from the ground bar at the subpanel and if installed in a separate building must have it’s own ground electrode with a solid #6 copper wire attached from electrode to the ground bar. The main service panel ground bar must be bonded and the subpanel unbonded.

Do you use a bonding screw on a subpanel?





Quote from the video:
Quote from Youtube video: But in this case. The bonding screw is that green headed screw right there. So that screw just simply threads through the neutral bus.

Where does the neutral wire go in a sub panel?

Since you are connecting the feed from the sub-panel to the main panel, it really doesn’t make any difference where you connect the neutral and ground, since they are bonded (connected) in the main panel.

Can I tie the neutral and ground together?

No, the neutral and ground should never be wired together. This is wrong, and potentially dangerous. When you plug in something in the outlet, the neutral will be live, as it closes the circuit. If the ground is wired to the neutral, the ground of the applicance will also be live.

Can ground and neutral be on same bus bar?

If the main service panel happens to be the same place that the grounded (neutral) conductor is bonded to the grounding electrode, then there is no problem mixing grounds and neutrals on the same bus bar (as long as there is an appropriate number of conductors terminated under each lug).

Should a subpanel have a ground rod?



Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building. And yes, a sub panel in the same building as the main does not need a ground rod – only the ground wire.

Does a 240v sub panel need a neutral?

A 240v only panel has no need for a neutral, I have panels in a industrial facility with no neutral, but for residential my jurisdiction requires a 4 wire feed or 3 with conduit as a ground even for all 240v loads.

Does a subpanel need to be grounded to the main panel?

Most panels come with a bar joining the two, which is easily removed. Code requires subpanels to have a ground connection that’s independent of the main panel’s.

Why is neutral bonded ground?



Quote from the video:
Quote from Youtube video: So this means that under any short circuit condition. Every piece of metal throughout the entire. Place is going to have current have fault current on it just like the neutral.

Why are the ground and neutral connected?

It is common on larger systems to monitor any current flowing through the neutral-to-earth link and use this as the basis for neutral fault protection. The connection between neutral and earth allows any phase-to-earth fault to develop enough current flow to “trip” the circuit overcurrent protection device.

How do you install a ground bar in a sub panel?

Quote from the video:
Quote from Youtube video: From the neutral bus of my first origination of power at the cutoff panel okay that wire comes in and that hooks into our first ground bar.

What is the difference between a neutral bar and a ground bar?

Neutral bars have a heavy, high-current path between the bar and neutral lug, which is itself isolated from the chassis It is obvious that the neutral lug-to-bar connection is heavy, and designed to flow a lot of current all the time. Ground bars are, by design, in direct contact with the panel chassis.

Why is there no ground bar in my panel?



You don’t have a ground bus because you don’t need one. All existing wiring is in metal conduit, which provides the ground. If you are in a location where local electrical code requires metal conduit, then by definition all your new circuits will have metal conduit as the ground path.

Can I add another neutral bar to a panel?

So the neutral bars have thermal considerations ground bars do not, as well as, you don’t want current to normally be present on the panel chassis, which is grounded. So you cannot add additional neutral bars, but they provided enough neutral slots for your needs, so you are all set.

Can you pigtail neutral wires in panel?

Pigtails in a panel are fine



Wire-splicing and pigtailing within a loadcenter cabinet (panel enclosure) is expressly permitted by NEC 312.8(A), and is quite safe (provided the splices are made up properly, of course): (A) Splices, Taps, and Feed-Through Conductors.

Can you double up wires on neutral bar?

As long as both existing bars are connected by a link bar or other path you can use either side for neutrals. Grounds typically can be two and even three conductors to a hole, sized #14 or #12 and sometimes #10, and must be the same size. So if you need to make room you can double up on some grounds.