When would you use a multi-wire branch circuit?

Multiwire branch circuits are used in offices, hospitals, hotels, high-rise residential buildings, or similar facilities for a variety of power distribution systems including lighting, devices, and receptacles.

What are the requirements for multi-wire branch circuits?





Remember, a multiwire branch circuit “consists of two or more ungrounded conductors that have a voltage between them, and a grounded conductor that has equal voltage between it and each ungrounded conductor of the circuit and that is connected to the neutral or grounded conductor of the system.”

What is an advantage of utilizing the three wire multi-wire branch circuit?

Multi-wire branch circuits
A Multi-wire branch circuit takes advantage of this, by extending both ungrounded conductors and sharing a single grounded (neutral) conductor. So instead of having two circuits requiring four conductors, you can have two circuits with only three conductors.

What happens in a multi-wire branch circuit when the grounded neutral opens or becomes disconnected?

If the grounded (neutral) conductor is accidentally opened, the circuit changes from two separate parallel 120 V circuits to one 240 V series circuit. This can result in fires and the total destruction of electrical equipment.

Can you share a neutral with multiple circuits?

as long as the phase conductors are on different “phases” it’s fine. Recent code requires them to be on a double pole breaker though. I do it as much as possible in houses. It’s easier to pull one three wire for two circuits, than 2 separate two wires.

Are multi wire branch circuits legal?





The National Electrical Code permits multiwire branch circuits, but adds requirements to make them safer. Section 210.4(B) states that in the panelboard where the branch circuit originates, all ungrounded conductors must be provided with a means to disconnect them simultaneously.

Can you share a neutral on GFCI breaker?

“The only way to use two GFCI receptacles to provide GFCI protection to more than two total receptacles on a shared-neutral circuit is to stop sharing the neutral after the GFCIs – by using two seperate 12/2’s, or 12/2/2.

Does NEC allow shared neutrals?

Sharing neutral or yoke
The NEC does not define multiple circuits. However, relating to 210.7, it appears to mean more than one circuit, on separate phases and each with its own neutral. If the circuits were on the same phase, simultaneous disconnection in the panelboard would not be possible.

Can dedicated circuits share a neutral?

A dedicated vs separate circuit is the argument– As I seeit a dedicated circuit should not share a neutral and a separate circuit may share it.

Can a multiwire branch circuit be used to supply the two required kitchen circuits?



1 states that a multiwire branch circuit can supply other than line-to-neutral loads if it supplies only one piece of utilization equipment. Exception No. 2 permits other than line-to-neutral loads where all of the ungrounded (hot) conductors are opened simultaneously by the branch-circuit overcurrent device.

When installing a multiwire branch circuit a means must be provided to simultaneously?

disconnect simultaneously

Fig. 3. Multiwire branch circuits that supply devices (or equipment) on the same yoke must also be provided with a means to disconnect simultaneously all ungrounded conductors that supply those devices (or equipment) at the point where the branch circuit originates [210.4(B)].

Are multiple branch circuits required to be provided with a means that will simultaneously all grounded conductors at the point the branch circuit originates?



Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates.

Can multiple circuits share a ground?

The code requires each branch circuit to have an equipment ground (either a wire, or conduit, or cable tray as in 250.120A), they can be shared when they are in the same raceway. If all the 20A circuits are in one raceway then you just need one ground.

Can you touch neutral wire?

If you touch the neutral wire in a live circuit, whether it be a lamp, an appliance or something else, it is the same as touching the active wire. It is only “safe” to touch the neutral wire when there is no current flowing, just as it is “safe” to touch the earth wire (when one exists).

How many hot wires can share a neutral?

One neutral may not have two “hot” wires from the same phase. It is good practice to use four (4) pole Circuit breakers (as opposed to the standard three pole) where the fourth pole is the neutral phase, and is hence protected against over current on the neutral conductor.

What happens if the live wire touches the neutral wire?



In an electric iron being used in a household, the plastic insulation of live wire and neutral wire in the connecting cable gets torn. Due to this, naked live wire touches the naked neutral wire directly and the electric fuse of the circuit blows off.

Can two circuits share a breaker?

Yes, it’s fine to combine circuits onto one breaker, at which point they become one circuit.

Why would a neutral wire be hot?

If the neutral is disconnected anywhere between the light bulb and the panel, then the neutral from the light to the point of the break in the neutral will become hot (and the device will be unpowered, because no current will be flowing through it).

Can I use a ground as a neutral?

A ground is not a neutral period. The last thing you want is the chassis of your washer as a current carrying conductor. If your house has a bonded neutral and ground then it should be at only at one connector and that is your circuit breaker panel and nowhere else.

Why am I getting 120 volts on my neutral?



If you have a neutral wire removed from the neutral bus bar in your panel it is possible to see 120VAC on that wire if the circuit breaker for that circuit is turned on and there is a load connected to the circuit and load device is also turned on.