Once you have the conduit in the ground, you have three basic possibilities open to you:

  1. Run a feeder (either full size or tapped) off the 200A breaker to a subpanel at the shed.
  2. Run a 20A hybrid branch/feeder to the shed that is tapped to feed the existing 20A receptacles using a 20A, 2-pole, common-trip breaker.

Can I feed a sub panel from the bottom?

Really depends on the panel. Many are designed for top feed or bottom feed, others do have a side that must be the top. Most of the time is dictated by installed breakers – including the main. If any handle operates up-down there is likely a proper up side.

How do you feed a subpanel from the main panel?





Quote from the video:
Quote from Youtube video: Goes into the panel. And on to the ground burn. Everything is connected ready to heat this up at the main panel we've completed the other panel. We've completed this panel.

Does a sub panel need a feeder breaker?

If the main panel’s MAIN breaker is of a size that will adequately protect the feeder wires and the subpanel, then no breaker is needed.

How many wires do I need to feed a subpanel?

This is typically a three-wire cable with three insulated conductors plus a bare copper ground wire. The cable must have a wire gauge sufficient to the amperage of the subpanel—a 100-amp subpanel requires #4 copper wires or, more commonly, #2 aluminum wires, for example.

How do I add a subpanel to a full breaker box?

Quote from the video:
Quote from Youtube video: You're going to be adding a subpanel always add the largest panel that that is practical to a door if you were thinking that you needed six circuits.

Does it matter if the main breaker is on top or bottom?





The NEC code provision that a breaker “ON” must be in the up position means that most panels can only use half of the breaker slots if mounted sideways.

Can you feed a subpanel through a breaker?

If the wire size from the sub panel is the size that the main breaker in the panel being fed from you don’t have to have the breaker but this means if you have a 200 a main breaker in that panel the wire ampacity will need to be that large.

Does a subpanel need a ground rod?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building.

Where does the ground go on a sub panel?

Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

Can you feed a subpanel with 3 wires?



Another way to wire a subpanel was with a three-wire feed; two hots and a neutral, with grounds and neutrals connected together at the subpanel. In this case, the grounds and neutrals have to be connected together.

Do you need 4 wires for a subpanel?

The current NEC code requires a 4-wire feeder so there is a separate grounding connector between the Main and Sub panels. The neutral and ground are not bonded in the subpanel.

How far can subpanel be from main panel?

The right feet would be between 4.5 to 5 feet.



The cable running from your main panel to the subpanel depends on the amperage rating. For instance, for a 30A panel, use a 10 AWG, three-wire conductor.

Can you run a 100 amp sub panel off a 100 amp main panel?



Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A. You can for example add a 60A breaker to your existing panel and protect the new subpanel with a 100A rating.

Can I run a 100 amp sub panel off 200 amp main?

Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn’t overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance,

Can you run a 200 amp sub panel off 200 amp main?

Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

How big of a subpanel can I install off a 200 amp service?

Even though there is no limit on the number of subpanels that you can add to a circuit, it shouldn’t exceed 160 amps when you’re using a 200 amp main panel. Always follow this guide to install subpanels effectively.

Can you daisy chain sub panels?



Answer: Yes. The main electrical service panel is where branch circuits originate. A branch circuit consists of the circuit conductors between the final over-current device protecting the circuit and the lights, receptacles and equipment supplied by the branch circuit.

Can I use aluminum wire to feed a subpanel?

Safety concerns caused aluminum wire to be banned from use in branch circuits years ago, but it is a common option for feeding main service panels and subpanels.

What wire do you use for a 200 amp service?

The Short Answer: For a 200 amp service, you’ll need a #4/0 aluminum wire.

Is copper or aluminum better for service entrance?

Choosing a Service Entrance Cable



Aluminum service entrance cables are cheaper, lighter, and generally easier to install, whereas copper cables are more durable with superior electric conductivity.