https://youtu.be/0TQ27NH4ppI

Should I bond the neutral to ground subpanel?

Here it is: Your ground and neutral wires definitely need to bond (or connect) together. But this is ONLY allowed in the main panel— never a subpanel, or anywhere else in the home. This is a very common mistake we see in the electrical part of your inspection.

Why does the neutral and ground have to be separated at the sub-panel?





With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!

How do you isolate neutrals?

Quote from the video:
Quote from Youtube video: Um is made and the service first point of disconnect is and at that point the neutrals and grounds must be bonded together to the neutral utility to the grounding electrode.

How far can a sub-panel be from the main?

You may not know this voltage, so it’s best to provide 4 feet. The panel must be easily accessible, so don’t install it too far above the floor; 4.5 to 5 feet is about right. The cable you run from the main panel to the subpanel also depends on the amperage rating.

Why are the neutral and ground bonded at the main panel?

The reason we sometimes bond the neutral and ground wire in the main panel is for cost savings. There is no electrical engineering advantage in this bond; it is there because it is often cheaper to install a jumper wire than it is to route a ground wire all the way from the transformer to the panel.

Do I need to bond neutral and ground?





If the ground is not bonded to neutral, then the entire ground circuit in the building becomes close to hot until the circuit breaker trips.

Can you combine neutral and ground in main panel?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Does a subpanel need to be grounded to the main panel?

Most panels come with a bar joining the two, which is easily removed. Code requires subpanels to have a ground connection that’s independent of the main panel’s.

Can ground and neutral be on same bus bar?

If the main service panel happens to be the same place that the grounded (neutral) conductor is bonded to the grounding electrode, then there is no problem mixing grounds and neutrals on the same bus bar (as long as there is an appropriate number of conductors terminated under each lug).

Can I run a 100 amp sub panel off 200 amp main?



Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn’t overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, …

Can you feed a 100 amp sub panel with a 60 amp breaker?

You can feed a 100 Amp panel with a 60 Amp breaker. Keep in mind that the sub panel needs to be rated above the breaker size.

Can you run a 100 amp sub panel off a 100 amp main panel?

Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A.

How many subpanels can you have on a 200 amp service?



Even though there is no limit on the number of subpanels that you can add to a circuit, it shouldn’t exceed 160 amps when you’re using a 200 amp main panel. Always follow this guide to install subpanels effectively.

Can I run a 200 amp sub panel off 200 amp main?

Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

Can a sub panel feed a sub panel?

Can I run a subpanel from a subpanel? Generally speaking, yes. You could put a million subpanels in series, and by itself that wouldn’t be a code violation. The metal conduit can act as the equipment ground so a 4th wire is not required.

What is the 6 breaker rule?

The “six breaker throw rule” was a requirement in the National Electrical Code that a service must have have a main disconnect that shuts off all power and it cannot take more than six switch throws to do it, and the main disconnect(s) also must be clearly marked, as in the photo above.

Can you daisy chain electrical sub panels?



Answer: Yes.



A branch circuit consists of the circuit conductors between the final over-current device protecting the circuit and the lights, receptacles and equipment supplied by the branch circuit.

How many wires do I need to feed a subpanel?

This is typically a three-wire cable with three insulated conductors plus a bare copper ground wire. The cable must have a wire gauge sufficient to the amperage of the subpanel—a 100-amp subpanel requires #4 copper wires or, more commonly, #2 aluminum wires, for example.

Can you feed a 100 amp sub panel with a 50 amp breaker?

Just wire it up. There is no problem using a sub panel that can take more current than you will ever feed it. Points to note: The cable to your hot tub will be rated for 50A (not 100A); therefore you must not upgrade the breaker in your main panel to 100A.

How do you feed a subpanel from the main panel?

Quote from the video:
Quote from Youtube video: Goes into the panel. And on to the ground burn. Everything is connected ready to heat this up at the main panel we've completed the other panel. We've completed this panel.