Can I put a sub panel in a shed?

Adding a Subpanel



For example, if you have 200-amp main service, you’ll have no problem adding a 100-amp subpanel to feed a shed, garage, or barn. A 60-amp subpanel can power lighting and general-use outlets in another section of your home.

How far can a subpanel be from the main panel?





The right feet would be between 4.5 to 5 feet.



The cable running from your main panel to the subpanel depends on the amperage rating. For instance, for a 30A panel, use a 10 AWG, three-wire conductor.

Does a subpanel need a separate ground?

The biggest difference between a subpanel and a main panel is that the ground and neutral buses on a subpanel have to be separated. Most panels come with a bar joining the two, which is easily removed. Code requires subpanels to have a ground connection that’s independent of the main panel’s.

Does a subpanel need to be bonded?

Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

Does a garage subpanel need a main breaker?

The subpanel may be equipped with a main breaker to allow for power interruption without having to go back to the main panel, but it is not required to have a main shutoff circuit breaker, since the feeder breaker back in the main panel serves this function.

How many electrical sub panels are allowed?





Even though there is no limit on the number of subpanels that you can add to a circuit, it shouldn’t exceed 160 amps when you’re using a 200 amp main panel. Always follow this guide to install subpanels effectively.

Is there a minimum height for a subpanel?

The panel only has to have 30” wide measured from one side or the other or centered or the width of the panel if larger than 30” , the door has to open to 90 degrees and the height of the working space 6-1/2′ no minimum for height .

Where do you place a subpanel?

Quote from the video:
Quote from Youtube video: The concept is that you want to be able to turn off all the power very quickly in a separate building so having a main gives you one spot to do that or if it's less than six breakers.

What is the electrical code for sub panel?

___ NEC 110.26(A) – The working space about electrical service panel/sub-panel shall be at least 3 ft. in front of the electrical panel. The width of the working space shall be 30” or greater, and the height of the space shall extend from the floor to 6 1/2 feet or the height of the panel, whichever is greater.

How do you wire a subpanel for a shed?



Quote from the video:
Quote from Youtube video: Already through some of the drywall into the main panel. So 30 amps was around the max with the voltage drop for the distance.

Does a subpanel in the same building need a ground rod?

You must, must, must, in every case run a ground ~ from the main to the subpanel. Doesn’t matter if you’re running it 3 feet, to an outbuilding or up a space elevator. You have to run a ground ~ or you are out of Code.

Why do you separate grounds and neutrals in a subpanel?

With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!

Does a sub panel in a shed need a disconnect?



It’s ok for a subpanel to have a main disconnect, but it’s not required. In this case, the disconnect was located outside of the condo unit. On condo buildings, it’s common for all of the main panels to be located in a single room, usually in the basement of the building.

What is the 6 breaker rule?

The “six breaker throw rule” was a requirement in the National Electrical Code that a service must have have a main disconnect that shuts off all power and it cannot take more than six switch throws to do it, and the main disconnect(s) also must be clearly marked, as in the photo above.

What is the difference between a main panel and a sub panel?

The main panel is directly connected to the point of entrance to a building, and all sub-panels feed off that connection. However, the sub-panel provides a useful methodology for installing outlets that help you organize your electrical system into something more manageable.

How do I choose a subpanel?

Subpanel Circuit Breaker Sizing



To calculate the breaker size, simply divide the adjusted wattage by 240 volts to find the rated amperage needed for your subpanel. Often, the result is not a common circuit breaker size.

When should I add a subpanel?



An electrician might add a sub panel to take the load off of the main circuit breaker panel. This can prevent overloading the electrical system and tripping circuit breakers or melting fuses. Sub panels are also used to separate the electrical needs of specific areas.

Can subpanel be bigger than main panel?

if the subpanel’s main breaker is larger than the supply breaker, it has no effect. if smaller than the supply breaker, the subpanel’s main breaker protects the subpanel.

What size breaker do I need for a subpanel?

Based on your question, since you will be having a subpanel, you want the breaker feeding the subpanel to be sized for the subpanel or slightly smaller. So if you purchase and install a 200A subpanel, then the breaker should be 200A. If you use a 125A subpanel, then use a 125A breaker.

How many circuits can be on a 60 amp subpanel?

Modern 60-amp electrical panels are purpose-built as sub-panels and generally only have 8 to 10 slots available for circuit breakers.