Can two branch circuits share a neutral?

What is a multiwire branch circuit? A multiwire branch circuit is a branch circuit with a shared neutral. This means there are two or more ungrounded (hot) phase or system conductors with a voltage between them and a shared neutral.

Can you tie neutrals together from different circuits?





As these joined neutrals include the travelers of both three-way circuits, the neutrals from the nearest light to each box, and the neutral heading back to the panel from each box, these two circuits’ neutrals have multiple junction points that tie the neutrals together.

How do you fix a shared neutral?

Quote from the video:
Quote from Youtube video: Then locate the shared neutrals in the electrical box and remove the wire connectors that splicing them all together then separate and identify each circuits to neutral conductors.

What is neutral sharing?

A shared neutral is a connection in which a plurality of circuits use the same neutral connection. This is also known as a common neutral, and the circuits and neutral together are sometimes referred to as an Edison circuit.

Is it OK to share a neutral?

as long as the phase conductors are on different “phases” it’s fine. Recent code requires them to be on a double pole breaker though. I do it as much as possible in houses. It’s easier to pull one three wire for two circuits, than 2 separate two wires.

How many phases can share a neutral?





If it is a 3 phase circuit you can have 3 hots per neutral as long as you are using the A, B & C phases for each neutral. A neutral is a current carrying conductor and must be the same size as the hot. The reason you can use 3 hots on a 3 phase circuit is because of the 120º differences between the phases.

Can you daisy chain neutral?

Most electricians wire electrical receptacles in this daisy-chain series. Ground connections on daisy-chained receptacles: Notice that only the hot and neutral wires are daisy-chained through the receptacle’s screws and copper strap.

Can you put 2 neutral wires together in a breaker box?

Panel manufactures and the code



The majority of the panel manufactures recommend only one neutral per slot. City building inspectors and home inspectors will normally call out this condition and recommend correction.

Can I pigtail a neutral wire?

If this is indeed how it’s wired (likely), then yes, wire the two existing neutrals together, add a pigtail neutral to go to the receptacle, and tie in the neutral from the smart switch. For reliability it is best to connect the pigtail to a screw terminal rather than a backstab, but they are electrically the same.

Can you touch the neutral wire?



If you touch the neutral wire in a live circuit, whether it be a lamp, an appliance or something else, it is the same as touching the active wire. It is only “safe” to touch the neutral wire when there is no current flowing, just as it is “safe” to touch the earth wire (when one exists).

What is the difference between neutral and ground?

Ground and Neutral are two important conductors apart from the hot (or phase or live) wire in a typical mains AC Supply. Neutral wire acts as a return path for the main AC while Ground acts as a low impedance path to “ground” fault current.

What is a dedicated neutral?

A dedicated line is a power line, which runs from the circuit breaker panel to the critical load and has no other loads connected to it. Normally a circuit breaker feeds multiple receptacles; with a dedicated line, a single circuit breaker feeds only the one receptacle that the protected load is connected to.

Does NEC allow shared neutrals?



Sharing neutral or yoke



The NEC does not define multiple circuits. However, relating to 210.7, it appears to mean more than one circuit, on separate phases and each with its own neutral. If the circuits were on the same phase, simultaneous disconnection in the panelboard would not be possible.

Can 2 circuits share a ground?

The code requires each branch circuit to have an equipment ground (either a wire, or conduit, or cable tray as in 250.120A), they can be shared when they are in the same raceway. If all the 20A circuits are in one raceway then you just need one ground.

Can arc fault breakers share a neutral?

Can the AFCI with shared neutral be used for retrofit installations? Yes, for retrofit installation, GE AFCIs can be substituted for the existing thermal magnetic breakers without the need to sort out existing shared or mixed neutrals.

Do arc fault breakers need a dedicated neutral?

To meet the latest version of the NEC, if AFCI protection is required on the shared neutral circuits being wired, you will be unable to use a 1-pole AFCI breaker, because it requires a dedicated conductor for the line and neutral.

Do bedroom lights need to be on an AFCI?



Anyway, NEC 2014 requires AFCI for all outlets in bedrooms and many other habitable rooms. The word “outlet” in NEC connotes any appliance that is served by electricity, including installed laods like lights, smart switches and the like.

Can GFCI and AFCI be on the same circuit?

Can a separate AFCI Receptacle and a GFCI Receptacle be used on the same circuit? Yes, they both can be used on the same circuit; however, the Dual Function AFCI/GFCI Receptacle offers the option of providing both AFCI and GFCI protection in a single device.

When should you not use AFCI?

Exception: AFCI protection is not required for extension wiring that is less than 6 ft long (raceway or cable) if no outlets or devices are added (other than splicing devices). This measurement does not include the conductors inside an enclosure, cabinet, or junction box.

Do kitchen counter plugs need to be arc fault protected?

Yes. Arc fault protection is required for the extension of the branch circuit. An AFCI receptacle (or a dead front) is required to be installed at the first added receptacle on the extension of the circuit.