Subpanel Circuit Breaker Sizing To calculate the breaker size, simply divide the adjusted wattage by 240 volts to find the rated amperage needed for your subpanel. Often, the result is not a common circuit breaker size. and you can simply round up to the next higher size of ​the breaker.

What size breaker do I need for a subpanel?

Based on your question, since you will be having a subpanel, you want the breaker feeding the subpanel to be sized for the subpanel or slightly smaller. So if you purchase and install a 200A subpanel, then the breaker should be 200A. If you use a 125A subpanel, then use a 125A breaker.

What size wire do I need to run a 100 amp subpanel?





The cable must have a wire gauge sufficient to the amperage of the subpanel—a 100-amp subpanel requires #4 copper wires or, more commonly, #2 aluminum wires, for example.

What size wire do I need to run a 60 amp subpanel?

In short, the wire size for a 60 amp sub-panel 150 feet away is 3 AWG gauge wire.

What wire do you use for a 200 amp subpanel?

The 250 KCMIL wire is the perfect size wire for 200 amp service because it has 255A ampacity (a minimum of 250A ampacity requirement is satisfied).

Can a 60 amp breaker feed a 100 amp sub panel?

You can feed a 100 Amp panel with a 60 Amp breaker. Keep in mind that the sub panel needs to be rated above the breaker size.

Can you run a 100 amp sub panel off a 50 amp breaker?





It’s a rating.



It’s the same with subpanels: The “100A” is a maximum rating. Do not exceed 100A. However, you certainly should exceed your feed-breaker size of 50A. Even if 50A panels existed, they would be very small in terms of numbers of spaces.

What wire size do I need to go 100 feet for a 100 amp service to a workshop?

If you check the wire size chart (you have the link in the introduction), the #0 AWG wire (also known as 1/0 AWG wire) has 150 ampacity. That means that #0 AWG wire is the perfect size wire for 100 amp service 100 feet away.

What size wire will a 100 amp breaker accept?

For 100 AMP service, you’ll need a #4 AWG copper wire or #2 AWG aluminum or copper-clad wire. Make sure to limit your voltage drop to 3% regardless of distance.

Can 4 AWG handle 100 amps?

#4 copper is good for 85 amps which means that you can go up to the next standard size which is 90 amps. If you want to use a 100 amp OCPD you will need to increase your conductor size #3 copper.

Can you run a 200 amp sub panel off a 200 amp panel?



Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

What size wire do I need to run 200 amp Service 200 feet?

For a 200 amp service, you’ll need: #2/0 copper wire, or. #4/0 aluminum or copper-clad aluminum wire.

How do you wire a 200 amp sub panel from a 200 amp main panel?


Quote from Youtube video: In front of me you see two main lugs that your main lugs it ties in the two black wires though the black and red in a black wire.

How many breakers can you put in a 60 amp sub panel?



Modern 60-amp electrical panels are purpose-built as sub-panels and generally only have 8 to 10 slots available for circuit breakers.

How many amps is #6 wire good for?

6 gauge wire can handle anywhere from 32 amps to 60 amps (check 6 Gauge Wire Amps Chart further on). This depends on copper vs aluminum wire and temperature.

What size wire do I need to run 60 amps 100 feet?

What size wire should I use for a 60 amp subpanel? You can get away with 6 AWG when you have a short run of wire, however, due to voltage drop, if you ever decide you want to go more than 100 feet then a 4 AWG is the size you should choose.

Can you run a 100 amp sub panel off a 100 amp main panel?

Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A.

Can you run a 200 amp sub panel off 200 amp main?



Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

Can I run a 100 amp sub panel off 200 amp main?

Can you add a 100 amp breaker to your main panel? Yes you have 12 slots the double pole breaker will only take 2 slots.

How many breakers can you have in a 30 amp sub panel?

The amount of current that is required for the connected loads can only be supported by a 30 Amp sub-panel. The maximum quantity of branch circuits can be determined with a load calculation. Two 15amp breakers or one 15amp and one 20amp can be used on a 30amp circuit.

Can I run a sub panel off a 30 amp breaker?

You need 10-gauge, three-conductor cable to wire a 30-amp subpanel. This cable has two hot wires (usually colored red and black), a white neutral wire and a ground wire, which is usually bare but could be green. It carries electricity at 240 volts, so you must treat it differently than regular 120-volt electric cable.

Can a 30 amp breaker feed a sub panel?



To summarize the last 8 comments: There is nothing wrong with having 4 15amp circuits in a sub-panel that has a 30 amp main breaker. You can use max 15 amp on any one circuit, and max 30 amp all combined.

What wire do I use for a 30 amp breaker?

A 10-gauge wire



If you look into a 30 Amp wire size chart online, the recommended size is a minimum of 10-gauge wire. A 10-gauge wire can safely carry the amount of current loads supplied by a 30-amp circuit.

Can you run 12 gauge wire on a 30 amp breaker?

You should not use a 30-amp circuit breaker on a 12-gauge wire. The circuit breaker installed on a circuit is of a specific size to protect a certain wire gauge. A larger breaker on a thinner wire will allow more current over the wire before tripping.

How far can you run 10 gauge wire on a 30 amp circuit?

How far can you run 10 gauge wire for 30 amps? 10-gauge wire is usually used for short 30 amp runs. If you plan on going over 150 feet, 8-gauge wire or thicker will be needed.