What kind of wire do you use for a subpanel?

The cable must have a wire gauge sufficient to the amperage of the subpanel—a 100-amp subpanel requires #4 copper wires or, more commonly, #2 aluminum wires, for example. (Aluminum is often used for feeder cables because the cost is typically much lower than that of copper wires.)

What type of cable is used for feeders?





Open wire or twin feeder: Apart from coax cable, another type of feeder that is more commonly used on frequencies below 30 MHz is called an open wire, twin feeder or ribbon. This type of feeder consists of two parallel wires.

Can I use SER cable to feed a sub panel?

SER is a perfect cable for feeding power to your sub-panel, and, depending on the amount of amps their sub-panels are handling (we’ve seen everywhere from 50 amp to 200 amp sub-panels being serviced), our customers are using all sizes of SER as a sub-panel feeder.

Does a subpanel feeder need to be in conduit?

Re: Subpanel wire run



Individual THHN conductors must be run in conduit–either metallic or non-metallic, flexible or rigid. You could probably use SER instead, as long as it’s sheathed and contains four conductors: one for Leg A, Leg B, neutral, and ground.

Can you run a 100 amp sub panel off a 100 amp main panel?

Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A. You can for example add a 60A breaker to your existing panel and protect the new subpanel with a 100A rating.

Can you run a 100 amp sub panel off a 200 amp main panel?





Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn’t overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, …

How do you size a feeder wire?

Quote from the video:
Quote from Youtube video: Basic rule is you size the feeder conductor sizing at 125. Percent of the continuous load plus the non continuous load will change theorists we've always done.

What type of cable is used for feeders and branch circuits?

Type MC cables are widely used in 600 volt and MV power, lighting and control applications. They are permitted for use on services, feeders and branch circuits for power, lighting, control and signaling circuits in accordance with Article 330 and 725 of the NEC.

What type of cable is suitable for direct burial?

Common types of cables with a copper conductor suitable for direct burial are USE-2, UF-B Underground Feeder Cable, and Tracer Wire. Aluminum URD Direct Burial Wire is the most commonly used direct burial aluminum wire. Let us focus on these cables in more detail to help you understand the difference.

Do service wires need to be in conduit?



So, you’ll either need to have this service-entrance re-run with a conduit, or see if you can get your local electrical inspectors to sign off on using bollards (i.e. concrete-filled metal poles) to protect the meter pan and service cabling as Machavity suggests.

How do I add a subpanel to my garage?

Quote from the video:
Quote from Youtube video: Turn it off next I found a nearby stud and pre-drilled holes for a plywood backer to map the sub panel. On. These two screws are for actually mounting the Sun panel.

Does a subpanel need a ground rod?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building. And yes, a sub panel in the same building as the main does not need a ground rod – only the ground wire.

Does a subpanel in a detached garage need a ground rod?



A detached building with a subpanel needs its own ground rod, regardless of if there are three wires or four wires feeding it.

What is code for outlets in garage?

210.52(G)(1) Garages.



In each attached garage and in each detached garage with electric power, at least one receptacle outlet shall be installed in each vehicle bay and not more than 1.7 m (5 ½ ft) above the floor.

Do garage outlets need to be GFCI protected?

GFCI protection is required for 125-volt to 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to the ground. GFCI receptacles are required in bathrooms, garages, crawl spaces, basements, laundry rooms and areas where a water source is present.

Do garage lights need to be GFCI protected?

NEC 210.8. 2 requires all outlets in a garage to be GFCI protected so if your lights are connected by an outlet they need GFCI protection if they are hard wired they do not require GFCI protection.

Do garage outlets need to be AFCI?



The 2017 National Electrical Code (NEC) requires the protection of an arc fault circuit interrupter (AFCI) for 15 and 20 amp circuits in all newly built residential areas, but they are not needed in bathrooms, garages, or outdoor areas.

How many outlets can a GFCI protect?

There’s no limit. A standard GFCI will protect up to 20 amps, drawn from any combination of receptacles, either the built-in one or any number of additional ones connected to its load terminals.

Why is there a GFCI in my garage?

GFCIs are required in garages because they prevent “ground fault” situations that can result in electric shock. Ground faults cause more than 80% of all electrical equipment failure and can be caused by: Worn insulation. Moisture.