Yes, that’s fine. The NEC specifically allows multiple 15A receptacles on a 20A branch circuit. You must use 12Ga or larger (if in copper) for all wiring – any 14 and you must use a 15A breaker.

Can you put a 15amp receptacle on a 20Amp breaker?

Most household electrical receptacles have a 15-amp rating, but they connect to a 20-amp circuit. You can use a device that has a 15-amp plug with either a 15- or 20-amp receptacle. Standard 15-amp receptacles are suitable for typical household appliances, lamps and other accessories.

Can you mix 15 amp and 20 amp outlets on a 20 amp circuit?





For instance, it is crucial that the amperage of an outlet doesn’t exceed the amperage of the circuit it uses. As a result, both 15 amp and 20 amp electrical sockets can be installed to a 20 amp circuit, yet only 15 amp receptacles should be used for 15 amp circuits.

How many outlets can you put on a 20 amp breaker?

The answer to the question how many outlets on a 20 amp circuit is ten outlets. Always comply with the 80% circuit and breaker load rule, allowing a maximum load of 1.5 amps per receptacle. Remember that your circuit, wire sizes, and outlets must be compatible to avoid overheating and electrical hazards.

Can I use 14 gauge wire on a 20 amp circuit?

NEC 240.4(D)(3) states that 14 AWG must be protected at 15A. You can not use 14 AWG anywhere on a circuit that has a 20A breaker.

What happens if you use 14 2 wire on a 20 amp circuit?

If the outlets are on a 20-amp circuit, 14/2 wire is not sufficient. You will have to step up to 12/2 wire for all outlets on 20-amp circuits. Using 14-gauge wire (such as 14/2) to wire outlets on a 20-amp circuit can result in overheating and a dangerous electrical fire.

How far can you run 12 2 wire on a 20 amp breaker?





After these distances, the circuit will go over the recommended 3% voltage drop. You can run a 12 gauge wire up to 70 feet on a 15 amp circuit. That number drops to 50 feet if you run 12 gauge wire on a 20 amp circuit.

Can you run lights on a 20 amp circuit?

Maximum Lights Per Circuit
Technically, you can install 13 outlets or lights on a 20-amp CB, but you can only put ten lights per circuit due to the 80% rule of maximum continuous load.

What size wire should I use for 20 amp breaker?

#12 AWG wire

The perfect wire gauge of a 20 amp breaker is the #12 AWG wire. This is a bigger wire with 25A ampacity and can handle 20 amp current while also satisfying the NEC 80% rule for safety.

Can you mix 12 gauge and 14 gauge wire on a 15 amp circuit?



There is nothing against code mixing wire size for these circuits as long as the OCPD matches the smallest wire. We ask them to mark the wires with tags in the panel so that in the future and for final inspection, we know what is what.

What is a backstab receptacle?

If an outlet is backstabbed, it means that the neutral wires (white) and hot wires (either red, blue or yellow) are pushed into small holes in the back of an outlet instead of being anchored down by screws.

How many outlets can you put on a 15 amp breaker?

8 outlets



Technically, you can have as many outlets on a 15 amp circuit breaker as you want. However, a good rule of thumb is 1 outlet per 1.5 amps, up to 80% of the capacity of the circuit breaker. Therefore, we would suggest a maximum of 8 outlets for a 15 amp circuit.

Is it OK to mix wire gauges?

The short answer is yes, different gauge wiring can be used on a single circuit. It’s done all the time when a long portion of a run is upsized to minimize voltage drop, then reduced again to accommodate termination limitations.

Can I pigtail 12 and 14 gauge wire?

Yes. It’s no problem as long as you can get a good twist on the wires. Pig tails can be 14 gauge since the branch circuit is protected by a 15A Breaker.

Can you splice Romex in a wall?

You can’t splice it in the wall or use a j-box that would be buried (code). You will need to back pull it and replace the run to the fixture. Concealed splicing is not permitted. The only correct way to splice is replace the section and/or do the splice in accessible junction boxes.