2 AWG copper2 AWG copper or larger.

What size wire do I need for a 70 amp sub panel?

The rule of thumb that techs will usually go by is that for a 70 amp circuit breaker, 4-gauge copper wire is the right one to go with. For an 80 amp, you need a 4-gauge copper wire. For a 100 amp service, you will need a 1-gauge wire. For 125 amps, you will need a 1-gauge copper wire.

What size wire do I need for 100 amp service 300 ft away?





for 300 feet for 100 amp rated service I would use Aluminum direct burial 1/0-1/0-1/0-1/0, the forth can be as low as #4 for the ground (but also in conduit, even if in conduit must still be rated underground wire and required by code also) Also note the size wire the breaker can handle, cannot cut strands to make fit, …

What size wire do I need for 100 amp service 100 feet away?

If you check the wire size chart (you have the link in the introduction), the #0 AWG wire (also known as 1/0 AWG wire) has 150 ampacity. That means that #0 AWG wire is the perfect size wire for 100 amp service 100 feet away.

What size wire do I need to run 60 amps 100 feet?

4 AWG

What size wire should I use for a 60 amp subpanel? You can get away with 6 AWG when you have a short run of wire, however, due to voltage drop, if you ever decide you want to go more than 100 feet then a 4 AWG is the size you should choose.

What is a 70 amp breaker used for?





Double-pole breaker

The 15-amp and 20-amp breakers often handle baseboard heaters, 30-amp serve water heaters and electric dryers, 40- and 50-amp are for electric ranges, and the 70-amp could serve a large air conditioner or a subpanel.

What gauge wire do I need for a 60 amp sub panel?

It is common to wire 60-amp breakers with 6-gauge, 3-conductor wire because an appliance that needs a 60-amp breaker rarely draws the full 60 Amp. It’s a good idea to connect a 60-amp subpanel to the main panel with 4-gauge wire.

What wire size do I need to go 200 feet for a 60 amp service to a workshop?

For 60 ampere breakers, electricians and professionals suggest using a wire size gauge ranging from 6 AWG to 4 AWG. All household wires have a rating of at least 600V, so only amperage really matters when it comes to determining wire gauge. Therefore, the wire size for 60 amp 220v, for example, is still 6 to 4 AWG.

What is 350 MCM wire?



This wire features a 350 AWG stranded bare copper conductor, PVC insulation, and a Nylon jacket. This bare copper building wire has a voltage rating of 600V and a maximum temperature of 90°C. It is suitable for use as general-purpose wiring for installation in conduit, cable trays, or other recognized raceway.

What size wire is needed for a 100 amp sub panel?

The cable must have a wire gauge sufficient to the amperage of the subpanel—a 100-amp subpanel requires #4 copper wires or, more commonly, #2 aluminum wires, for example. (Aluminum is often used for feeder cables because the cost is typically much lower than that of copper wires.)

Can 8 gauge wire handle 60 amps?

An 8-gauge copper wire can handle 50 amps at 167 degrees F but an 8-gauge aluminum wire at the same ambient temperature rating will only carry 40 amps. Overall, you need a 4-gauge wire or greater to handle 60 amps.

How far can you run 6 gauge wire for 50 amps?



For every 100 feet, voltage drops by 20%.

Example: 50 amp wire is usually the 6 AWG (we require at least 62.5A and 6 AWG can handle 65A). If you have to power an electric device 100 feet away, you need 20% amps more.

Can number 6 wire carry 60 amps?

This is what all those homeowners that mistakenly use 6 AWG gauge wire for 60 amp breaker don’t take into account. 6 AWG can only handle 65 amps. Here’s what a professional will know: The next wire size that can handle more than 75 amps (as required for a 60 amp breaker) is the 4 AWG gauge wire.

What size wire do you need for 80 amps?

80-amp service requires a 2-gauge wire. If you exceed 80 amps, you should jump to 1 gauge. The next size after 1-gauge is 2/0, followed by 3/0. It should be noted that you can only use 2 or even 3-gauge wire if the material is copper.

What is 8 gauge wire rated for?



According to NEC, 8-gauge copper wire can handle a maximum of 40-55 amps while 8 gauge aluminum wire can handle a maximum of 30-45 Amps. 8 gauge wire can withstand 40 – 55 amps.

Can 8 gauge wire handle 50 amps?

No not safe to use a 50 amp breaker. The only time a 50 amp would be ok with #8 woul be if these were individual thhn wires in conduit. You need a 40 amp breaker. If the stove specifically calls for a 50 amp breaker the wire does need to be replaced in order to use a 50 amp breaker.

How many amps is 1 ought wire good for?

Wire Size and Amp Ratings

Wire Size 75°C (167°F)
AWG (mm²) Copper
1 (42.4) 130
1/0 (53.5) 150
2/0 (67.4) 175

What wire is needed for 220v 50 amp?

As you can see from the graph, a 6 AWG is the safe choice if you have a 220v 50 amp that you need to power. A 12-gauge is the right wire size for your 220v 20 amp needs.

How many amps is number 8 Romex good for?



Size & AMP Ratings

NM, TW, & UF WIRE (Copper Conductor) SE CABLE (Copper Conductor)
12 AWG – 20 AMPS 6 AWG – 65 AMPS
10 AWG – 30 AMPS 4 AWG – 85 AMPS
8 AWG – 40 AMPS 2 AWG – 115 AMPS
6 AWG – 55 AMPS 1 AWG – 130 AMPS

Which is thicker 8 gauge or 10 gauge wire?

Which is thicker 8 gauge or 10 gauge? The general rule of thumb is that the smaller the gauge number, the thicker the cable. The standardized method of measuring the thickness of a cable was established in 1857 in the United States.

What is the maximum amperage for 14 gauge wire?

20 Amps

According to the “powers-that-be”, a 14 gauge wire can carry 20 Amps, but only as a built-in safety measure.