Why Wire Gauge Is Important

Wire Use Rated Ampacity Wire Gauge
Low-voltage lighting and lamp cords 10 amps 18-gauge
Extension cords (light-duty) 13 amps 16-gauge
Light fixtures, lamps, lighting circuits 15 amps 14-gauge
Kitchen, bathroom, and outdoor receptacles (outlets); 120-volt air conditioners 20 amps 12-gauge

How do I know what size electrical wire to use?

To determine what gauge wire you need, consider the carrying capacity and the amount of current the wire needs to conduct (measured in amperage or amps). Wire gauge is directly related to how many amps you need to run through it. The distance you need the wire to go can also impact the gauge of wire you need.

Should I use 14 or 12-gauge wire?





12-gauge wire is the minimum requirement for outlets on a 20-amp circuit. 12-gauge wire can be used for outlets on both 15 and 20-amp circuits. 14-gauge wire is unsafe to use for outlets on a 20-amp circuit. 14-gauge wire can only be used for outlets on a 15-amp circuit.

What is the proper wire size for home wiring?

In terms of home electrical wire, you’ll usually be working with 12 or 14-gauge wire. But for appliances, you’ll be using 10, 8, or 6 gauge. Things like stoves, water heaters, dryers, and air conditioning units use these larger gauges because they require a lot of amperages.

Can I use 12 gauge wire on a 15 amp breaker?

Because it has even less chance of overheating, 12-gauge wire is also acceptable on a 15-amp circuit.

Can you use 12 and 14 gauge wire together?

Anyway, the first subject is a bit touchy because it makes it difficult to perform an inspection when all of the wires coming into the panel are 12 but many of the circuits have 14 in them too. There is nothing against code mixing wire size for these circuits as long as the OCPD matches the smallest wire.

What happens if you use 14 gauge wire on a 20 amp circuit?





I would say 14 gauge wire anywhere on a 20 amp circuit is not OK. The purpose of the breaker is to cut off power before the wiring overheats. If you plug in several devices on an outlet that total 20 amps, you will exceed the safe working capacity of the 14 gauge wire without tripping the breaker.

Can I use 14 3 wire for outlets?

Quote from the video:
Quote from Youtube video: You can also use 14 3 wire if you are installing multi-branch circuits meaning you are using the black wire for phase a and the red wire for phase b.

Is 14 gauge wire OK for a 20 amp circuit?

14 AWG can’t be used on a circuit with a 20A breaker. The screw terminals are the better choice if you want to put 15 Amp receptacle on a 20 Amp circuit with 12 gauge wire. You can use the side terminals.

How many outlets can be on a 15 amp circuit?

8 outlets



Technically, you can have as many outlets on a 15 amp circuit breaker as you want. However, a good rule of thumb is 1 outlet per 1.5 amps, up to 80% of the capacity of the circuit breaker. Therefore, we would suggest a maximum of 8 outlets for a 15 amp circuit.

Can you put 15 amp receptacles on a 20 amp circuit?

The amperage of the outlet must never exceed the amperage of the circuit. According to National Electrical Code, only a 15-amp or 20-amp electrical receptacle can be installed to a 20-amp circuit. A 15-amp receptacle may also be installed on a 15-amp circuit.

How far can you run 12 gauge wire on a 20 amp circuit?

After these distances, the circuit will go over the recommended 3% voltage drop. You can run a 12 gauge wire up to 70 feet on a 15 amp circuit. That number drops to 50 feet if you run 12 gauge wire on a 20 amp circuit.

How many receptacles can be on a 20 amp circuit?



The answer to the question how many outlets on a 20 amp circuit is ten outlets. Always comply with the 80% circuit and breaker load rule, allowing a maximum load of 1.5 amps per receptacle. Remember that your circuit, wire sizes, and outlets must be compatible to avoid overheating and electrical hazards.

How far can you run 12-gauge wire without a voltage drop?

As an example, for a 120-volt circuit, you can run up to 50 feet of 14 AWG cable without exceeding 3 percent voltage drop.



For 240-volt circuits:

14 AWG 100 feet
12 AWG 120 feet
10 AWG 128 feet
8 AWG 152 feet
6 AWG 188 feet