turn off all the breakers on the ‘red’ side of the subpanel. Check if the main breaker still trips. If it does not, the issue is with whatever hooked up to that side (shorted wire, etc) If it still does, swap with the ‘black’ breaker to see if the breaker itself is the problem.

Can you back feed a sub panel?

It is not physically possible for the MAIN and the Generator to both be turned on at the same time. The only way you could have it go into the sub-panel would be if the sub-panel was interlocked to disconnect from the main panel, so you absolutely cannot feed the main from the sub, no way, no how.

Why are neutrals and grounds separated in a subpanel?





With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.)

Do sub panels need to be grounded?

Answer: No. You’d need at least one grounding electrode, or ground rod, for every sub-panel in a detached building. Whether you need two or not is determined by the soil and local regulations. So, check your local code requirements.

How many wires can be in a subpanel?

A subpanel requires two hot wires connected to a 240-volt double-pole breaker in the main panel. It also needs a neutral wire and a ground wire. The cable used for this run is known as a “three-wire cable with ground.” The two hot wires, called feeder wires, will provide all of the power to the subpanel.

What is a backfeed breaker?

In a panelboard application, a back-fed main breaker is mounted on the branch bus, occupying normal branch breaker mounting space or circuits, instead of in the separate, vertical position more typical of a main breaker.

Can I wire a subpanel from a subpanel?





Answer: Yes. The main electrical service panel is where branch circuits originate. A branch circuit consists of the circuit conductors between the final over-current device protecting the circuit and the lights, receptacles and equipment supplied by the branch circuit.

Can neutral and ground be on the same bar in main panel?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Can I tie the neutral and ground together?

No, the neutral and ground should never be wired together. This is wrong, and potentially dangerous. When you plug in something in the outlet, the neutral will be live, as it closes the circuit. If the ground is wired to the neutral, the ground of the applicance will also be live.

Should a subpanel have a ground rod?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building. And yes, a sub panel in the same building as the main does not need a ground rod – only the ground wire.

Why does a subpanel need 4 wires?



The neutral and ground are not bonded in the subpanel. In this setup if a hot wire coming in contact with the non-current carrying parts of the electrical system, (outlet covers, panel covers etc), the 4th ground conductor will provide a low resistance patch back to the source tripping a breaker.

Do you use a bonding screw on a subpanel?

Quote from the video:
Quote from Youtube video: But in this case. The bonding screw is that green headed screw right there. So that screw just simply threads through the neutral bus.

Does a sub-panel need a main breaker?

A main breaker on a sub-panel is not necessary because this is in the same building (if you are in a different building then NEC 225.31, 225.32, 225.33 apply). That said, having a main breaker in the sub-panel is also acceptable.

What is the 6 breaker rule?



The “six breaker throw rule” was a requirement in the National Electrical Code that a service must have have a main disconnect that shuts off all power and it cannot take more than six switch throws to do it, and the main disconnect(s) also must be clearly marked, as in the photo above.

Can you run a 100 amp sub panel off a 100 amp main panel?

Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A.

Can you feed a 100 amp sub panel with a 60 amp breaker?

You can feed a 100 Amp panel with a 60 Amp breaker. Keep in mind that the sub panel needs to be rated above the breaker size.

Can I run a 100 amp sub panel off 200 amp main?

Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn’t overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, …

What size breaker do I need for a subpanel?



Based on your question, since you will be having a subpanel, you want the breaker feeding the subpanel to be sized for the subpanel or slightly smaller. So if you purchase and install a 200A subpanel, then the breaker should be 200A. If you use a 125A subpanel, then use a 125A breaker.

How many breakers can I run off a 60 amp subpanel?

Modern 60-amp electrical panels are purpose-built as sub-panels and generally only have 8 to 10 slots available for circuit breakers.

Can a 60 amp breaker feed a 60 amp sub panel?

Probably not. While the 60A breaker’s primary job is to protect the wiring between the panel and the subpanel, you can have breakers totaling more than 60A in the subpanel.

How do I know if my electrical panel is overloaded?

The most obvious sign of an electrical circuit overload is a breaker tripping and shutting off all the power. Other signs can be less noticeable: Dimming lights, especially if lights dim when you turn on appliances or more lights. Buzzing outlets or switches.