What is the minimum size grounding conductor for 100amp service?

You are correct that for a 100A feeder, the associated ground wire needs to be an 8AWG copper or 6AWG aluminum wire.

Does sub panel wire need to be in conduit?





Re: Subpanel wire run

Individual THHN conductors must be run in conduit–either metallic or non-metallic, flexible or rigid. You could probably use SER instead, as long as it’s sheathed and contains four conductors: one for Leg A, Leg B, neutral, and ground.

Can a grounded conductor be installed outside of a raceway?

Equipment grounding conductors shall be permitted to be installed outside a raceway or cable assembly where in accordance with the provisions of 250.130(C) for certain existing installations or in accordance with 250.134, Exception No. 2, for dc circuits.

What size grounding electrode conductor for 200 amp panel?

What Size Grounding Wire is Required for a 200 Amp Service? A grounding wire ranging from 2AWG to 8 AWG is recommended for a 200-amp service. You can use 8AWG (Copper) or 6 AWG (Aluminum) grounding wires for a 200-amp service. You can also use copper conductors of 4AWG and aluminum conductors of 2AWG.

What size wire do I need to run 100 amp Service 150 feet?





What Size Wires are Needed for an AMP Service Upgrade?

Service or Feeder Rating Copper Conductors Minimum Conduit Size
100 Amps #4 AWG 1 ¼ inch
125 Amps #2 AWG 1 ¼ inch
150 Amps #1 AWG 1 ¼ inch
200 Amps #2/0 AWG 1 ½ inch

Do you need a ground rod for a sub panel?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building. And yes, a sub panel in the same building as the main does not need a ground rod – only the ground wire.

What size wire do I need to run a sub panel?

The cable you run from the main panel to the subpanel also depends on the amperage rating. You can use 10 AWG, three-conductor wire for a 30-amp panel, but for a 60-amp one, you need 6 AWG wire. If you’re installing a 100-amp panel, you need 4 AWG copper or 2 AWG aluminum three-conductor cable.

Can I run service-entrance cable in conduit?

Yes, you can run service-entrance cable (SER) in conduit, but it can’t be run underground, either in or out of conduit.

What is the difference between ser and Seu?



Basically, SER is a round service electrical cable that typically has up to four conductors and a bare neutral. The cable is designed to use above the ground in feeder panels and branch circuits. SEU is an unarmored Style U flat service electrical cable with two-phase conductors and a concentric neutral.

What diameter ground rod do I need?

The minimum allowed diameter for a ground rod is 3/8″, but larger sizes are a better choice because they provide more surface area to contact the earth.

How big does a ground rod need to be?

The ground rod or pipe: shall not be less than 1.5 m (5 ft) in length and 12.7 mm (1/2 in.) in diameter; driven, where practicable, into permanently damp earth; and.

What size ground do I need?



Table 250.122 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment

Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Conduit, etc., Not Exceeding (Amperes) Size (AWG or kcmil)
Copper Aluminum or Copper-Clad Aluminum*
20 12 10
60 10 8
100 8 6

What is the minimum size solid conductor permitted to be installed in a raceway?

Yes, a solid bare copper 10 AWG equipment grounding conductor IS permitted in a metallic raceway. However, a bare aluminum conductor is NOT permitted in a metallic raceway. Also, conductors LARGER than 10 AWG installed in a raceway must be stranded.

What size feeder overcurrent device is required for a 100a continuous load?

What size protection device and conductor is required for a 100 ampere continuous load, Figure 4. Step 1. The branch circuit overcurrent protection device must have an ampacity of not less than 125% of the continuous load [210-20(a)], 100 amperes X 1.25 = 125 amperes = 125 ampere protection.

Does ground wire need to be same gauge?

The ground wire, hotwire, and neutral wire should be of the same gauge. Because the gauge size is determined by the load current. Neutral wire returns the same load current in hotwires. For that reason, the wire size has to be the same.

What happens if your ground wire is too small?



With too-small a ground wire, the breaker cannot magnetic-trip because it cannot flow enough current to hit 10x, because of the too-high resistance of the wire.

Can a wire be too big?

using larger wire will not hurt anything or cause any overload. The larger wire will cost more, the pathway or where it has to fit, and the physical size of the connecting means (ie. the size of terminal or clamp it has to fit in), will all be determining factors in just how big is too big.

Can ground wire be downsized?

The answer is no if you’re looking for a simple answer. More complex answer – What everyone is trying to say in the comments is that you can size the wire according to Table 250.122 in the NEC. This table allows you to size the equipment grounding conductors according to the breaker size protecting the circuit.

Does negative wire need to be same size as positive?

Ampacity (determined by conductor material, gauge, length and insulator material heat rating) of both positive and negative wires needs to be the same. It’s a Good Life.

Can any wire be used as a ground wire?



type – yes, but it is best to use an oxygen free, multi strand wire thats meant to be used in car audio to keep interference out and corrosion down. also, it is a lot easier to deal with since its a lot more flexable then solid wire.