No, don’t do that… Me, I’d choose a panel with a main breaker and remove the bonding screw – they are often no more expensive than those without a main, and sometimes less expensive since they move in volume. And there’s no debate… Thank you for your answer.

What is the difference between a main lug only and main circuit breaker load center?

Main Lug Only



A main lug type load center does not have a main circuit breaker. The incoming supply cables are connected directly to the main lugs and bus bars. Primary overload protection for the load center is not provided as an integral part of the load center.

Does a sub panel in a separate building need a main breaker?





The subpanel may be equipped with a main breaker to allow for power interruption without having to go back to the main panel, but it is not required to have a main shutoff circuit breaker, since the feeder breaker back in the main panel serves this function.

Do load centers have a main breaker?

Load centers can be equipped with a main breaker or main lug only (MLO) design. In a load center with a main breaker design, the incoming supply cables are connected directly to the main circuit breaker.

Are neutral and ground bonded in meter?

Meter equipment should never be bonded to both the equipment grounding conductor and the neutral. This practice can create parallel paths for neutral current to flow on the equipment grounding conductor between equipment and service disconnect. It may flow across surfaces of sockets and enclosures.

Can you install a main breaker in a main lug panel?

Main breakers can be installed when the meter and feeder cable are within 10-feet of the panel. Consult your local codes to see if your panel will meet this or another requirement for proper installation. Main lug panels do not have a main breaker.

Can I use a main panel as a sub panel?





There’s no problem with having a main breaker in a subpanel. It’s required if your panel is in a separate building and has more than six breakers, but there’s nothing prohibiting it in any other case.

Does a sub panel need to be bonded?

Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

Why do you not bond a sub panel?

So, why do you separate the ground and neutral in a subpanel? Because when we bond them together, it gives your neutral wire (the one carrying electrical currents BACK to the source) multiple pathways. That’s how the chassis of some equipment will become energized.

How far can a subpanel be from the main panel?

The right feet would be between 4.5 to 5 feet.



The cable running from your main panel to the subpanel depends on the amperage rating. For instance, for a 30A panel, use a 10 AWG, three-wire conductor.

Can neutral and ground be connected together in main panel?



The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Why do you have to bond the neutral and the ground wire in the main panel?

With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel.

Where do you bond ground and neutral?

Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are “bonded” to earth ground at either the electrical service entrance, or at transformers within the system.

Does a sub panel need a ground rod?



Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building.

How many amps can a 100 amp panel handle?

For example, a 100-amp service panel could have circuit breakers that add up to more than 200 amps.

How do you run a wire from the main panel to a subpanel?


Quote from Youtube video: Cover then of course we're going to need our feeder wire coming from our main panel over to our sub panel and in this case we're going to be running three gauge copper.

Can you run a 100 amp sub panel off a 100 amp main panel?

Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A.

Can I run a 100 amp sub panel off 200 amp main?



Can you add a 100 amp breaker to your main panel? Yes you have 12 slots the double pole breaker will only take 2 slots.

Can you run a 200 amp sub panel off 200 amp main?

Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

Can you daisy chain sub panels?

Answer: Yes. The main electrical service panel is where branch circuits originate. A branch circuit consists of the circuit conductors between the final over-current device protecting the circuit and the lights, receptacles and equipment supplied by the branch circuit.

How many 220v outlets can you have on a 200 amp service?

Most 200-amp breaker panels have 40 to 42 slots of single-pole breakers or 20 slots for double pole breakers.