Does the NEC allow metal raceways to be used with nonmetallic boxes?

Yes. Where internal bonding means are provided between all entries, nonmetallic boxes shall be permitted to be used with metal raceways or metal-armored cables.

When nonmetallic enclosures for switches are used with metal raceways or metal-armored cables they shall ?





Metal enclosures for switches or circuit breakers used as service equipment shall comply with the provisions of Section E3609. 4. Where nonmetallic enclosures are used with metal raceways or metal-armored cables, provisions shall be made for connecting the equipment grounding conductor.

What is used to secure non metallic cables to an electrical box?

Nonmetallic-sheathed cable shall be supported and secured by staples, cable ties, straps, hangers, or similar fittings designed and installed so as not to damage the cable, at intervals not exceeding 1.4 m (4 ½ ft) and within 300 mm (12 in.) of every outlet box, junction box, cabinet, or fitting.

When mounting an enclosure in a finished surface the enclosure shall be?

An enclosure mounted in a finished surface shall be rigidly secured thereto by clamps, anchors, or fittings identified for the application. (D) Suspended Ceilings. An enclosure mounted to structural or supporting elements of a suspended ceiling shall be not more than 1650 cm3 (100 in.

What article of the NEC applies to nonmetallic boxes?

314.17(C) Nonmetallic Boxes and Conduit Bodies.
Where nonmetallic boxes and conduit bodies are used with messenger supported wiring, open wiring on insulators, or concealed knob-and-tube wiring, the conductors shall enter the box through individual holes.

Where are nonmetallic boxes used?





(C) Nonmetallic Boxes.
Where nonmetallic boxes and conduit bodies are used with open wiring or concealed knob-and-tube wiring, the conductors shall enter the box through individual holes.

Can you use a plastic box with MC cable?

MC Cable Is for Metal Boxes Only!
Plastic or fiberglass electrical boxes aren’t designed to be used with MC cable. Even if you’re able to rig up a connection to a plastic box, you will fail the electrical inspection.

Where nonmetallic boxes are used with open wiring and concealed?

(C) Nonmetallic Boxes and Conduit Bodies
Where nonmetallic boxes and conduit bodies are used with messenger-supported wiring, open wiring on insulators, or concealed knob-and-tube wiring, the conductors shall enter the box through individual holes.

Which of the following nonmetallic raceways is recognized in the NEC for protection of grounding electrode conductors from physical damage?

PVC conduit



In the 2017 NEC, PVC conduit was permitted to be used to protect a grounding electrode conductor from physical damage. In the 2020 NEC, PVC must now be schedule 80 if used to protect a grounding electrode conductor.

Can be used to secure boxes to a structural member using brackets on the outside of the enclosure?

Nails and screws

Nails and screws, where used as a fastening means, shall secure boxes by using brackets on the outside of the enclosure, or by using mounting holes in the back or in one or more sides of the enclosure, or they shall pass through the interior within 6 mm (1/4 in.)

What is a general NEC requirement for installing boxes?



Terms in this set (15) The following is a general NEC requirement for installing boxes? The finished installation must be accessible for future maintenance and repair.

What is code for electrical boxes?

Securing Cables
Article 334.30 states that cables coming out of the junction boxes should be secured within 12 inches of the box in all boxes equipped with cable clamps. These cable clamps are not to be removed. 314.17(C) states that cables must be secured to the receptacle box.

At what point are boxes required when wiring with non metallic sheathed cable?

Where the wiring method is conduit, tubing, Type AC cable, Type MC cable, Type MI cable, nonmetallic-sheathed cable, or other cables, a box or conduit body shall be installed at each conductor splice point, outlet point, switch point, junction point, termination point, or pull point, unless otherwise permitted in

Where are boxes required NEC?

A box shall be installed at each outlet and switch point for concealed knob-and-tube wiring. Fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed.

What does the NEC state about unused openings in nonmetallic boxes?



Unused openings in boxes shall be effectively closed. When openings in non-metallic boxes are broken out and not used, the entire box must be replaced. NEC 110-12 and 370-18 Unused openings in boxes shall be effectively closed.

Are round boxes allowed to be used with conduit?

Round boxes shall not be used where conduits or connectors requiring the use of locknuts or bushings are to be connected to the side of the box.

Where nonmetallic sheathed cable or multiconductor Type UF cable is used the sheath shall extend not less than?

6 mm

Where nonmetallic sheathed cable or multi-conductor Type UF cable is used, the sheath shall extend not less than 6 mm (1⁄4 in.) inside the box and beyond any cable clamp.

How many inches are required by the Code in mounting boxes behind the surface of non combustible materials?



1/4 inch

In walls or ceilings constructed of noncombustible material (concrete, tile, etc.), boxes must be installed so that the front edge will not be set back more than 1/4 inch from the finished surface.

What is considered a deep electrical box?

They are generally 2 x 3 inches in size, with depths ranging from 1 1/2 inches to 3 1/2 inches. Some forms are “gangable”—with detachable sides that can be removed so the boxes can be linked together to form larger boxes for holding two, three, or more devices side-by-side.

Where are junction boxes required?

You’ll need a junction box if you can’t make the connections inside an existing electrical box. You should install the box with the opening facing out from the wall so all the wires inside are accessible. Like any electrical box, it should be installed so that the edge of the opening is flush with the wall.