Can you mix wire sizes in conduit?

You’re fine on fill, but not by all that much



(Pro tip: for rough numbers on conduit fill — use metric units and round wire sizes up to the nearest integer, this makes the fill math quite a bit easier.)

How do you calculate conduit fill with different size conductors?





Quote from the video:
Quote from Youtube video: So there's three different things we need to take an account when calculating a conduit fill 1 the number of conductors that are being installed. 2 the total cross sectional area of the conductors.

How is conduit size calculated when wires of two or more sizes are used?

Multiply the number of wires for each gauge and type by the wire diameter. Total the results.

Can you run different wires in the same conduit?

Conduit thermal derate



Too many wires in a conduit will make more heat than the conduit can get rid of. Because of that, wires are de-rated when 4-6 wires run together in conduit.

Can you use two different gauge wires together?

It must be noted that while it is possible to splice different types of Romex wire—12/2 to 12/3, for instance—you should never splice together wires of a different gauge. Wire gauge is determined by the amount of amperage the wire is expected to carry.

Can I mix 10 and 12 gauge wire?





You haven’t said how you will manage the transition from 10 gauge to 12 gauge. If you are thinking of wire nuts in a junction box, then the answer is that you cannot do this safely. The 20A breaker’s job is to protect the load wire connected to it. A 12 gauge wire needs a 20A breaker to protect it.

How do you calculate filling ratio?

Simply divide the number of orders you’re able to fulfill completely by the number of total orders customers place. The result gives you a decimal, which you multiply by 100 to arrive at a percentage.

How do you figure conduit fill?

The National Electrical Code establishes that if a conduit only contains 1 wire, the max fill percentage is 53%. If it contains 2 wires, the max fill percentage is 31%. And if it contains 3 or more wires, the max fill percentage is 40%.

Can you run power and lighting in same conduit?

Per National Electric Code (NEC), Class 1 and Class 2 wiring are not permitted in the same enclosure, cable, or raceway. An exception to this rule is that Class 2 circuits can be reclassified if Class 1 requirements are met.

What size conduit do I need for 12 2 wire?



For two 12/2 NM cable, you need at least 1″ conduit (by calculations below) but it’ll still be a difficult pull. For two 12/2 UF, you’ll need at least 1-1/4″ conduit.

Can feeders and branch circuits in same conduit?

It’s true that service conductors must not be installed in the same raceway with feeder or branch circuit conductors, but line and load conductors for feeders and branch circuits can be in the same raceway or enclosure.

Why is it important to place all conductors of the same circuit in the same raceway?

If all of the conductors of a circuit are run closely together (in the same raceway for example) the magnetic fields of the conductors vary in opposition and cancel each other out. Inductive reactance results in power factor loss and the heating of metal enclosures.

Is a subpanel a branch-circuit?



Subpanel Power Supply



Answer: In short, yes. The main electrical service panel is where branch circuits originate.

What is a feeder NEC?

Article 100 defines feeders as: “All circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device.” The clumsiness of this wording makes this definition hard to follow.

How do you calculate feeder size?

Feeder No.

  1. I=kVA x 1000/(V x 1.732) I=569.19kVA x 1000/(13,800V x 1.732) I=23.82A. Feeder No.
  2. Amps at 13,800V=27.88A. Feeder No.
  3. I=kVA x 1000/(V x 1.732) I=192.57kVA x 1000/(13,800V x 1.732) I=8.06A. Feeder No.
  4. Amps at 13,800V=15A. Feeder No.
  5. I=kVA x 1000÷(V x 1.732) I=488.88kVA x 1000/(13,800V x 1.732) I=20.46A. Feeder No.


What is the difference between a branch-circuit and a feeder?



A feeder is the circuit conductors between the service equipment, the source of a separately derived system, or other power source and the final branch-circuit overcurrent device. Conductors past the final OCPD protecting the circuit and the outlet are branch-circuit conductors [Art.

What is the requirement for sizing conductors for continuous loads?

Sections 210.19(A), 215.2 and 230.42(A) require the conductor to be sized no less than 100% of the noncontinuous load, plus 125% of the continuous load. In addition, 110.14(C) requires consideration of the temperature rating of the equipment terminals when sizing conductors.

What is the 125 rule in electrical?

For branch circuits, NEC 210.19 states the rules for sizing conductors. The general rule is that conductors are sized to have an ampacity of not less than the noncontinuous load plus 125 percent of the continuous load.

What does the NEC consider A continuous load?

Because the term “continuous load” is in more than one article in the NEC, the definition is in Article 100. It is a load where the maximum current is expected to continue for three hours or more. Continuous load provisions pertain to branch circuits, feeders and services.