What wire do you run to a sub panel?

The cable you run from the main panel to the subpanel also depends on the amperage rating. You can use 10 AWG, three-conductor wire for a 30-amp panel, but for a 60-amp one, you need 6 AWG wire. If you’re installing a 100-amp panel, you need 4 AWG copper or 2 AWG aluminum three-conductor cable.

Does a sub panel need a feeder breaker?





If the main panel’s MAIN breaker is of a size that will adequately protect the feeder wires and the subpanel, then no breaker is needed.

How do you wire a 120 volt 30 amp sub panel?

Quote from the video:
Quote from Youtube video: We've got a three wire with a ground number 10 set that is feeding our panel for 30 amps. And when I say number 10 it's what number 10 is the wire that it takes to feed a 30 amp subpanel.

Where should feeder wires to a subpanel be connected?

Quote from the video:
Quote from Youtube video: The wire. Into the sub panel from the main panel. So we'll be running our six gauge ground wire. And our feeder wire next this is three gauge like I mentioned earlier anything six gauge or smaller.

What wire do I use for a 50 amp sub panel?

6 AWG





For 50 amps, you could use 4 AWG wire with 85A ampacity (a bit of overkill but it’s OK), but you can never use 8 AWG wire with 50A ampacity (you will fry the circuit). In most cases, 6 AWG is an almost perfectly-sized wire for a 50 amp breaker. In limited cases, you will probably have to use a larger 4 AWG wire.

What gauge wire do I need for 100 amp service?

Installation of 100 amp electric service or subpanel needs a #4 AWG copper wire or #2 AWG aluminum or copper-clad wire inside a minimum 1.25 inch, schedule 40 or 80 PVC electric conduit for underground service.

Can you run a 200 amp sub panel off 200 amp main?

Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

What size wire do I need to run 100 Amp Service 150 feet?

#00 AWG wire



Wire Size For 100 Amp Sub Panel 150 Feet Away



100 amp service 150 feet away from the sub panel requires #00 AWG wire (also known as 2/0 AWG wire). This wire has a median ampacity of 175 amps; more than enough than the required minimum 162.5 ampacity.

What wire do I use for a 30 amp sub panel?

You need 10-gauge, three-conductor cable to wire a 30-amp subpanel. This cable has two hot wires (usually colored red and black), a white neutral wire and a ground wire, which is usually bare but could be green. It carries electricity at 240 volts, so you must treat it differently than regular 120-volt electric cable.

Does a subpanel need a ground rod?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building.

Can you wire a subpanel with 3 wires?



Another way to wire a subpanel was with a three-wire feed; two hots and a neutral, with grounds and neutrals connected together at the subpanel. In this case, the grounds and neutrals have to be connected together.

What wire do I need for a 60 amp subpanel?

In short, the wire size for a 60 amp sub-panel 150 feet away is 3 AWG gauge wire.

What size is 200 amp service wire?

The Short Answer: For a 200 amp service, you’ll need a #4/0 aluminum wire.

Can ground and neutral be on the same bar?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Should subpanel be bonded?



Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

Why are neutrals and grounds separated in a subpanel?

With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.)

Where do you bond ground and neutral?

Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are “bonded” to earth ground at either the electrical service entrance, or at transformers within the system.

What happens if you don’t bond neutral?

That is as situation where a hot to ground short occurs, which is a very common fault. If the ground is not bonded to neutral, then the entire ground circuit in the building becomes close to hot until the circuit breaker trips.

What happens if earth and neutral wires touch?



If a neutral wire touches an earth wire, it creates a short circuit. This will cause the electricity to flow through the shortest path possible, which could result in a fire or an electric shock.