No, they do not need to be on “their own” circuit, but they do need to be tied into the primary circuit so they know when to turn on. Many, if not most, emergency lights are self powered, normally by battery, so “their own” circuit is limited to the emergency light.

Do emergency lights have to be on a dedicated circuit UK?

No they don’t need to be on their own circuit, and yes it would be sensible to feed them from the main lighting circuit.

In what particular locations that emergency light must be provided?

The IBC specifically requires emergency lighting in certain spaces not used for egress: electrical rooms, fire command centers, fire pump rooms, and generator rooms. No special performance characteristics are specified for these areas.

What is a maintained emergency lighting circuit?

Maintained Lights



Maintained emergency lighting is on at all times. Maintained emergency lights are mains powered and used as part of the normal room lighting system. But, in an emergency situation when mains power fails, it will continue to stay lit for a specific duration powered by a back-up battery.

What British standard must emergency lighting within premises comply to?

BS 5266

BS 5266: emergency lighting.

Are exit signs required to be on a dedicated circuit?

Exit signs/Emergency lights (Unit Equipment) not fed from the same circuit as the normal area lighting. Section 700.12(F)(2) requires the exit sign/emergency lights to be fed from the same circuit that provides the normal area lighting (check the exception).

What are OSHA requirements for emergency lighting?

There are no specific requirements that emergency lighting be provided in the OSHA Standards.

Does emergency lighting need to be hardwired?

If the electricity goes out, emergency lights must operate for a minimum of 90 minutes, according to the NFPA. In addition, the electrical supply must provide power within 10 seconds of the loss of normal power. Egress lighting must be “hardwired,” or served by the building’s primary electrical supply.

What is the difference between emergency light and exit light?

Light heads (lights on top or beside an exit sign) on exit signs are pointing towards the ceiling or side wall instead of an exit door. Areas such as internal rooms, bathroom and storage areas don’t have emergency lighting.

Does emergency lighting have to be wired in fire rated cable?

I’m well aware that emergency lights must be wired from the local lighting circuit and if from a central battery source the cables must be fire rated, if the lights are self contained then the cable should be the same as the local lighting circuit.

What are the legal requirements for emergency lighting testing?

Well, UK fire safety legislation stipulates that emergency lighting must undergo a full test once a year, and be ‘flick-tested’ at least once a month. The main purpose of this kind of lighting is to illuminate escape routes, although it also allows occupants to find fire-fighting equipment if there’s a fire.

Do emergency exit signs need to be illuminated?

Fire exit and escape route signs



All escape route signs require adequate illumination to ensure they can be seen and understood. They should also be visible under power loss conditions which may require artificial illumination. This does not mean the sign itself needs to be ‘illuminated’.

Who is responsible for emergency lighting?

The responsibility for emergency lighting rests with a ‘Responsible Person’, who has control, or a degree of control, over premises and fire-safety systems within premises. In English law a ‘person’ can be either an individual or an entity such as a limited company.

What is the electrical code for exit signs?

Exit Signs for doors and corridors should be mounted with the bottom of the exit no more than 80 inches (6’8″) above the top edge of the egress opening. Floor proximity exit signs require the bottom of the sign be mounted no less than 6″ from the floor and no more than 18″ above the floor.

How do you wire emergency exit lights?

Quote from the video:
Quote from Youtube video: Next we need to mount the canopy. We've determined that we're going to be installing this exit sign at 120 V AC. So we're gonna cut and cap the 277 V AC wire cutting is not required.

How do you wire an emergency lighting circuit?

Quote from the video:
Quote from Youtube video: Finally neutral often goes to the switch as well. So line conductor because it's be a twin and earth would come in connect. And the neutral to its neutral bar.

Can a emergency light be on a switch?

Switches connected in series or three- or four-way switches are not permitted in emergency lighting circuits. Additional switches that act only to put emergency lights into operation, but not disconnect them, are permitted.

Do emergency lights need a permanent live?

If they are maintained they will be switched on and off just like a normal light fitting, but they will have an additional live supply (called the permanent live, and which is un-switched) whose function is to keep the batteries fully charged.