The answer is never. Grounds and neutrals should only be connected at the last point of disconnect.

Should grounds and neutrals be separated in main panel?

The National Electrical Code (NEC) requirement for separated neutrals and grounding wires in a subpanel and separate neutral and grounding conductors back to the main panel, when both panels are in the same building, dates to the 1999 revision.

Can neutrals and grounds be connected together?





No, the neutral and ground should never be wired together. This is wrong, and potentially dangerous. When you plug in something in the outlet, the neutral will be live, as it closes the circuit. If the ground is wired to the neutral, the ground of the applicance will also be live.

What happens if you mix neutral and ground?

They could be electrocuted. Not good. So, to prevent this, the National Electrical Code prohibits the connection of the equipment ground and neutral at any point other than the service. So, normal current only flows on the neutral.

Why neutrals & grounds are connected in a main panel?

The reason we sometimes bond the neutral and ground wire in the main panel is for cost savings. There is no electrical engineering advantage in this bond; it is there because it is often cheaper to install a jumper wire than it is to route a ground wire all the way from the transformer to the panel.

Where do you bond neutral and ground?

Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are “bonded” to earth ground at either the electrical service entrance, or at transformers within the system.

Why do you separate grounds and neutrals in a subpanel?





With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!

Can you tie neutrals together from different circuits?

Tying neutrals of different circuits together is effectively paralleling wire, which unless larger than 1/0 is also a violation of 310.4. 300.3 references 310.4, tho 300.3 says all conductors of a circuit must be in the same cable, raceway, etc unless allowed elsewhere.

Can you double up ground wires in panel?

Each neutral (white, grounded conductor) wire should be secured separately under its own lug/set-screw terminal in an electric panel, per National electrical Code (NEC 408.41). Also, a neutral and equipment ground (bare or green) wire cannot share a terminal.

Should ground be bonded to neutral?

To provide the low impedance path necessary to clear a ground-fault from the separately derived system, the metal parts of electrical equipment shall be bonded to the grounded (neutral) terminal (Xo) of the derived system.

Does a subpanel need to be grounded to the main panel?



Most panels come with a bar joining the two, which is easily removed. Code requires subpanels to have a ground connection that’s independent of the main panel’s.

How do you ground a main electrical panel?

To add grounding to an existing panel, drive a ground rod into the ground and connect a grounding wire to the main electrical panel. Install new power outlets that have a continuous grounding path back to the grounding rod.

What happens if you don’t bond neutral?

That is as situation where a hot to ground short occurs, which is a very common fault. If the ground is not bonded to neutral, then the entire ground circuit in the building becomes close to hot until the circuit breaker trips.

How do you wire a neutral and ground in a breaker box?



On a main panel, you connect the ground wire from the new cable and the neutral (white) pigtail from the AFCI to the neutral bus. Route the AFCI neutral pigtail and ground wires to empty screws on the neutral bus and tighten.