Can I wire a subpanel with 3 wires?

Another way to wire a subpanel was with a three-wire feed; two hots and a neutral, with grounds and neutrals connected together at the subpanel. In this case, the grounds and neutrals have to be connected together.

Do I need 3 or 4 wires for subpanel?





The current NEC code requires a 4-wire feeder so there is a separate grounding connector between the Main and Sub panels. The neutral and ground are not bonded in the subpanel.

Is a sub panel considered a branch circuit?

Subpanel Power Supply
Answer: In short, yes. The main electrical service panel is where branch circuits originate.

Do all sub panels need to be grounded?

The sub panel neutral bar or terminal should not be bonded to the enclosure or the ground of the sub panel. The sub panel ground should not have a ground rod tied to it. The bonding for the main ground sources such as a ground rod is made at the main panel where all the grounds are bonded together as well.

Can neutral and ground be connected together in panel?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Does a subpanel need to be bonded?





Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

Do I need a ground rod at my sub panel?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building.

Do I need a ground rod for a subpanel in the same building?

You must, must, must, in every case run a ground ~ from the main to the subpanel. Doesn’t matter if you’re running it 3 feet, to an outbuilding or up a space elevator. You have to run a ground ~ or you are out of Code.

How many wires can be in a subpanel?

A subpanel requires two hot wires connected to a 240-volt double-pole breaker in the main panel. It also needs a neutral wire and a ground wire. The cable used for this run is known as a “three-wire cable with ground.” The two hot wires, called feeder wires, will provide all of the power to the subpanel.

Why do grounds and neutrals have to be separated in a sub panel?



With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!

Does a 240v sub panel need a neutral?

A 240v only panel has no need for a neutral, I have panels in a industrial facility with no neutral, but for residential my jurisdiction requires a 4 wire feed or 3 with conduit as a ground even for all 240v loads.

Does the neutral wire carry current?

To sum up, a live wire carries the full load current, while a neutral wire carries some current, only when the loads are not balanced.

Can I use ground as neutral?



A ground is not a neutral period. The last thing you want is the chassis of your washer as a current carrying conductor. If your house has a bonded neutral and ground then it should be at only at one connector and that is your circuit breaker panel and nowhere else.

Does single phase neutral carry current?

In single-phase, loads the neutral wire provides the return path for the current, and in balanced 3 phase loads, because they satisfy the above criteria, the currents enter and return through lines creating 0A of out of balance current. So, there is no need for a neutral wire.

What happens if you connect neutral to ground?

If the neutral breaks, then plugged in devices will cause the neutral to approach the “hot” voltage. Given a ground to neutral connection, this will cause the chassis of your device to be at the “hot” voltage, which is very dangerous.

Can you tie neutrals together from different circuits?

Tying neutrals of different circuits together is effectively paralleling wire, which unless larger than 1/0 is also a violation of 310.4. 300.3 references 310.4, tho 300.3 says all conductors of a circuit must be in the same cable, raceway, etc unless allowed elsewhere.

Where do you bond ground and neutral?



Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are “bonded” to earth ground at either the electrical service entrance, or at transformers within the system.