Can you run a 200 amp sub panel off 200 amp main?

Is feeding a 200A sub from a 200A main legit? Yes, and you don’t even need another 200A breaker. The 200A breaker alread present in the panel will suffice, and so you can use a subfeed lug kit as DrSparks advises.

How many amps can you pull off a 200 amp service?





In general, a 200-amp panel should handle no more than 160 amps at once. It’s important to note that people can have 300 or even 400 amps worth of breakers in a 200A panel, as they don’t use all circuits at the same time. Calculating how many circuit breakers you need is also dependent on your home electrical loads.

Can I run two 100 amp sub panel off 200 amp main?

Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn’t overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, …

What size conduit is needed for a 200 amp service?

Installation of 200 amp electrical service needs a #2/0 AWG copper wire or #4/0 AWG for aluminum or copper-clad wire inside a minimum of 1.5 inches, schedule 40 or 80 PVC conduit for underground service. However, 2 or 2.5 inches is recommended if running 3 wires in the same conduit.

How many breakers can I have in a 200 amp panel?

Most 200 amp panels will have 40 breaker slots but can accept more circuits with tandem breakers. 120v single-pole breakers will use 1 breaker slot, while 240v double-pole breakers will use 2 breaker slots. Manufacturers rate their panels and limit the number of electrical circuit breakers based on that rating.

Can subpanel be bigger than main panel?





if the subpanel’s main breaker is larger than the supply breaker, it has no effect. if smaller than the supply breaker, the subpanel’s main breaker protects the subpanel.

What size wire is good for 200 amps?

For a 200 amp service, you’ll need: #2/0 copper wire, or. #4/0 aluminum or copper-clad aluminum wire.

Can I use a main panel as a subpanel?

There’s no problem with having a main breaker in a subpanel. It’s required if your panel is in a separate building and has more than six breakers, but there’s nothing prohibiting it in any other case.

How far can a subpanel be from the main panel?

The right feet would be between 4.5 to 5 feet.



The cable running from your main panel to the subpanel depends on the amperage rating. For instance, for a 30A panel, use a 10 AWG, three-wire conductor.

How far can you run 200 amp service underground?



You’ll see that if you’re using 2/0 wire for 200A you’re almost certainly using copper, not aluminum. On 2020-07-02 by BILLY M. The distance is roughly 150 feet.

How many wires do I need for a 200 amp service?

RESIDENTIAL UNDERGROUND SERVICE INSTALLATION 100-200 AMP, 120/240 VOLT, 3 WIRE, SINGLE PHASE. 1 3 CONDUCTOR SERVICE TO HOUSE. SEE NOTE E. 2 NON METALLIC CONDUIT IF REQUIRED.

How far can I run electrical wire underground?

As an example, for a 120-volt circuit, you can run up to 50 feet of 14 AWG cable without exceeding 3 percent voltage drop.



For 240-volt circuits:

14 AWG 100 feet
10 AWG 128 feet
8 AWG 152 feet
6 AWG 188 feet

Can a main panel be used as a subpanel?



There’s no problem with having a main breaker in a subpanel. It’s required if your panel is in a separate building and has more than six breakers, but there’s nothing prohibiting it in any other case.

Can a sub panel have a main breaker?

The subpanel may be equipped with a main breaker to allow for power interruption without having to go back to the main panel, but it is not required to have a main shutoff circuit breaker, since the feeder breaker back in the main panel serves this function.

How do you hook up a sub panel to a main panel?

Quote from the video:
Quote from Youtube video: Together in the neutral bar because in the main panel the neutrals and grounds are bonded together by a bonding strap.

How big of a subpanel can I install off a 100 amp service?

Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A. You can for example add a 60A breaker to your existing panel and protect the new subpanel with a 100A rating.

What size wire is good for 200 amps?



For a 200 amp service, you’ll need: #2/0 copper wire, or. #4/0 aluminum or copper-clad aluminum wire.

How far can subpanel be from main panel?

The right feet would be between 4.5 to 5 feet.



The cable running from your main panel to the subpanel depends on the amperage rating. For instance, for a 30A panel, use a 10 AWG, three-wire conductor.

Can I run a subpanel off another subpanel?

Can I run a subpanel from a subpanel? Generally speaking, yes. You could put a million subpanels in series, and by itself that wouldn’t be a code violation. The metal conduit can act as the equipment ground so a 4th wire is not required.

What is the 6 breaker rule?

The “six breaker throw rule” was a requirement in the National Electrical Code that a service must have have a main disconnect that shuts off all power and it cannot take more than six switch throws to do it, and the main disconnect(s) also must be clearly marked, as in the photo above.

Can you daisy chain electrical sub panels?



Answer: Yes.



A branch circuit consists of the circuit conductors between the final over-current device protecting the circuit and the lights, receptacles and equipment supplied by the branch circuit.

Does a subpanel need a ground rod?

Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building.

Why do you not bond a sub-panel?

So, why do you separate the ground and neutral in a subpanel? Because when we bond them together, it gives your neutral wire (the one carrying electrical currents BACK to the source) multiple pathways. That’s how the chassis of some equipment will become energized.

Why do you separate the ground and neutral in a sub-panel?

With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!