Can a sub panel have a main breaker?

The subpanel may be equipped with a main breaker to allow for power interruption without having to go back to the main panel, but it is not required to have a main shutoff circuit breaker, since the feeder breaker back in the main panel serves this function.

How do you run a sub panel from the main panel?





Run the feeder cable from the main panel to the subpanel.

  1. You may need to remove a knockout slug to insert the wires into the main panel.
  2. There should be a black wire, red wire, white wire, and bare metal wire.
  3. If you’re installing a subpanel in a separate room from the main panel, use a longer feeder cable to reach it.

Can you run 2 sub panels off the main panel?

You can add as many subpanels as you need providing the combined electrical demand is below 160 amps. If all the circuitry was operating at once, the electrical service could become overloaded.

Does subpanel need ground from main panel?

Most panels come with a bar joining the two, which is easily removed. Code requires subpanels to have a ground connection that’s independent of the main panel’s.

Does a subpanel need a main disconnect?





It’s ok for a subpanel to have a main disconnect, but it’s not required. In this case, the disconnect was located outside of the condo unit. On condo buildings, it’s common for all of the main panels to be located in a single room, usually in the basement of the building.

Can you run a 100 amp sub panel off a 200 amp main panel?

Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn’t overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, …

Can you run a 100 amp sub panel off a 100 amp main panel?

Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A. You can for example add a 60A breaker to your existing panel and protect the new subpanel with a 100A rating.

How far can subpanel be from main panel?

The right feet would be between 4.5 to 5 feet.



The cable running from your main panel to the subpanel depends on the amperage rating. For instance, for a 30A panel, use a 10 AWG, three-wire conductor.

Can you feed a 100 amp sub panel with a 50 amp breaker?

Just wire it up. There is no problem using a sub panel that can take more current than you will ever feed it. Points to note: The cable to your hot tub will be rated for 50A (not 100A); therefore you must not upgrade the breaker in your main panel to 100A.

Can ground and neutral be on same bus bar on a sub panel?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Does a subpanel in same building need a ground rod?



Answer: No. You’d need at least one grounding electrode, or ground rod, for every sub-panel in a detached building. Whether you need two or not is determined by the soil and local regulations. So, check your local code requirements.

Why do you separate the ground and neutral in a sub panel?

With ground and neutral bonded, current can travel on both ground and neutral back to the main panel. If the load becomes unbalanced and ground and neutral are bonded, the current will flow through anything bonded to the sub-panel (enclosure, ground wire, piping, etc.) and back to the main panel. Obvious shock hazard!

Do you use a bonding screw on a subpanel?

Here it is: Your ground and neutral wires definitely need to bond (or connect) together. But this is ONLY allowed in the main panel— never a subpanel, or anywhere else in the home. This is a very common mistake we see in the electrical part of your inspection.

Can I connect neutral and ground together?

No, the neutral and ground should never be wired together. This is wrong, and potentially dangerous. When you plug in something in the outlet, the neutral will be live, as it closes the circuit. If the ground is wired to the neutral, the ground of the applicance will also be live.

Why are the neutral and ground bonded at the main panel?



The reason we sometimes bond the neutral and ground wire in the main panel is for cost savings. There is no electrical engineering advantage in this bond; it is there because it is often cheaper to install a jumper wire than it is to route a ground wire all the way from the transformer to the panel.

Does a subpanel need a neutral?

The neutral and ground MUST NOT be bonded at a sub-panel. They should only be bonded at the main service panel. If you bond them anywhere other than the main service, the neutral return current now has multiple paths, including though your ground wire.

Do you have to separate neutral and ground in main panel?

The National Electrical Code (NEC) requirement for separated neutrals and grounding wires in a subpanel and separate neutral and grounding conductors back to the main panel, when both panels are in the same building, dates to the 1999 revision.