What determines the rating of A branch circuit?

A: The size or rating of a branch circuit is determined by the ampere rating of the overcurrent device.

What is the minimum size branch circuit conductors?





When sizing branch-circuit conductors, the minimum branch-circuit conductor size shall have an allowable ampacity not less than 125 percent of the continuous load [210.19(A)(1)]. When sizing overcurrent protection, the overcurrent device rating shall not be less than 125 percent of the continuous load [210.20(A)].

What must the minimum ampacity be for most branch circuit conductors CEC?

The ampacity of branch-circuit conductors shall not be less than 125 percent of the designed potential load of utilization equipment that will be operated simultaneously.

How are branch circuits conductors sized?

Branch-circuit conductors shall have an ampacity not less than the maximum load to be served. Conductors shall be sized to carry not less than the larger of 210.19(A)(1)(a) or (b). For branch circuits not more than 600 volts, conductors shall have an ampacity not less than the maximum load to be served.

What is the maximum load on a 20 amp branch circuit?

A 20-ampere, 120-volt branch circuit will carry 2,400 volt-amperes (20 x 120 = 2,400). The maximum number permitted on a 20-ampere branch circuit is three (2,400 ÷ 750 = 3.2 = 3).

What is a 20 amp branch circuit?





210-23(a) 15- and 20-Ampere Branch Circuits A 15- or 20-ampere branch circuit can supply lighting units, other utilization equipment, or a combination of both. The rating of any one cord-and-plug-connected piece of utilization equipment must not exceed 80 percent of the branch-circuit ampere rating.

What is a branch circuit conductor?

Branch Conductors are the Circuits that provide power from the circuit breakers that are installed in the Service Panel which provide power to the Loads or Devices being powered from the Electrical Service Panel.

What is the 80 rule in electrical?

Unless otherwise marked, circuit breakers should not be loaded to exceed 80 percent of their current rating, where in normal operation the load will continue for 3 hours or more.

What is the 125 rule in electrical?

For branch circuits, NEC 210.19 states the rules for sizing conductors. The general rule is that conductors are sized to have an ampacity of not less than the noncontinuous load plus 125 percent of the continuous load.

What does AWG mean electrical?



American Wire Gauge

American Wire Gauge (AWG) is the standard way to denote wire size in North America. In AWG, the larger the number, the smaller the wire diameter and thickness.

How is the rating of the branch circuit protective device affected?

Branch circuits are rated using the rating of the maximum overcurrent protection device. How are branch circuits rated? There’s no change to the rating of the branch-circuit protective device.

Where connected to a branch circuit having a rating in excess of?



Where connected to a branch circuit having a rating in excess of 20 amperes, lampholders shall be of the heavy-duty type. A heavy-duty lampholder shall have a rating of not less than 660 watts if of the admedium type, or not less than 750 watts if of any other type.

What is the minimum number of 20 amp branch circuits required in a dwelling?

three

The minimum number of 20-ampere, 2-wire general-purpose branch circuits for lighting and receptacles in this dwelling is three. Be careful when calculating the minimum number of 20-ampere branch circuits.

When determining the load for recessed lighting fixtures for branch circuits the load shall be based on the?

Although 100-watt lamps will be installed, the load calculation must be based on the maximum wattage or volt-amperes. Each of these recessed luminaires must be calculated at 150 volt-amperes (see Figure 3).

How do you find the load on a branch circuit and how do you calculate maximum allowable amps?



Calculating Load

  1. Add together the wattage capacity of all general lighting branch circuits.
  2. Add in the wattage rating of all plug-in outlet circuits.
  3. Add in the wattage rating of all permanent appliances (ranges, dryers, water heaters, etc.)
  4. Subtract 10,000.
  5. Multiply this number by . …
  6. Add 10,000.

What is the definition of branch circuit?

The definition of a branch circuit is, “the circuit conductors between the final overcurrent device protecting the circuits and the outlet(s).” “Outlet” is defined as “[a] point on the wiring system at which current is taken to supply utilization equipment.” The Occupational Safety and Health Review Commission has held …

How many branch circuits are required in a home?

As mentioned in June, a minimum of two small-appliance branch circuits are required in kitchens. [210.52(B)(1)] Kitchen countertop surfaces have the same requirement. At least two small-appliance branch circuits are required to feed the receptacles that serve countertop surfaces in a kitchen. (See Figure 1.)

What is the maximum general purpose branch circuit rating of a flat conductor cable?

General-purpose and appliance branch circuits shall have ratings not exceeding 20 amperes. Individual branch circuits shall have ratings not exceeding 30 amperes.

Is a dedicated circuit a branch circuit?



The term “dedicated circuit” is a layman’s term for what the National Electric Code or NFPA 70 calls an “individual branch circuit”. Each item on an individual branch circuit has its own circuit breaker in the electrical box.

What residential branch circuits are required in modern homes?

There are several different types of branch circuits in your home.

  • Dedicated appliance circuits. These serve only one appliance and are often required by code. …
  • Lighting circuits. These are what they sound like—circuits that serve general lighting needs in rooms. …
  • Outlet circuits. …
  • Room circuits.

What are the three types of branch circuits?

Branch Circuits

  • General Purpose Branch Circuit.
  • Appliance Branch Circuits.
  • Individual Branch Circuit.

How do you find the number of branch circuits?

(a) The number of branch circuits required shall be determined in accordance with the following: (1) Lighting, based on 3 volt-amperes per square foot times outside dimensions of the manufactured home (coupler excluded) divided by 120 volts times amperes to determine number of 15 or 20 ampere lighting area circuits.