It is essential that the detection of the RCD is below the minimum anticipated current through the body and in fact the recommended tripping current for shock protection is a maximum of 30 mA and this is the current recommended in the Wiring Regulations.

What is the standard trip current for an RCD?

Whilst RCDs have a nominal tripping current (IΔn), they may trip below the nominal value; for instance, a 30 mA RCD is required to trip at a current between 18 mA to 28 mA.

How do I choose an RCD rating?





In summary, to choose the right type of residual current device, two different aspects must be considered:

  1. The type of RCD protection required: The type of RCD protection required.
  2. The type of fault current wave form: The type of fault current wave form. Go back to RCD types ↑


What does the amp rating on an RCD mean?

Each RCD rating refers to the maximum current the RCD should take. This means you can load the RCD with MCBs that draw current above the RCD rating provided you allow for diversity. So for example an Immersion Heater taking 16 amps has diversity of 1 because it is intended to take the 16 amps for a long time.

What is a 30 amp RCD?

30 Amp 30mA. 32 Amp 30mA. RCD’s Residual Current Device Offers Protection against Electric Shock. An RCD provides protection against earth faults occurring in equipment and reduces the effects of electric shock on human beings and thus saves lives.

Is a 100mA RCD OK to use in domestic?





A 100 mA RCD is not to be used for personal protection, it needs 30mA for this to the regulations in domestic properties, and I would also recommend it in this case, for commercial properties.

What is 500ma RCD used for?

The translation of regulation 605-10-01 (page 156 BS7671-2001) is that an rcd up to 500 mA may be used for protection against fire EXCEPT where the equipment is essential to the welfare of livestock. Agreed!



See Also:

Technical discussion forums
· Other and general engineering discussions
Archived categories

How is RCD calculated?

Quote from the video:
Quote from Youtube video: So uh 307 0.32 multiplied by 68 divided by 68 plus 307.32 so i'm getting 55.68 i'll run it off seven nine two six eight.

How fast should a 30ma RCD trip?

In fact, an RCD when tested at its rated sensitivity must trip in 300 ms. When tested at five times, ie, 150 mA for a 30 mA device, it should trip in 40 ms.

Can you overload an RCD trip?



RCD tripping will occur when a short circuit is identified. Overloads happen when electrical circuits are overwhelmed. This can happen if you plug too many appliances into one power point/adaptor or if appliance voltages and power board capacities have been mismatched.

What trips first 30mA or 100mA?

If it’s the main switch, then everything goes dark, and the occupants are left stumbling around looking for a torch. Fit a 100mA (or more) RCD up front, probably a time-delayed one, and it’s likely that a 30mA one will trip first. With some power left on, the occupants should still be able to see what they are doing.

Is 100mA better than 30mA?

Yes, 30mA is safer than 100mA. 10mA, the lowest standard size, is safer still. The actual device used depends on what is being protected, what it’s being protected against and the regulations applying to the location where it’s being used (both in terms of country, state etc.

What’s the difference between 30mA and 100mA RCD?



A 30mA RCD will save the majority of people in most circumstances when they come into contact with an energised part of the installation. A 100mA device in the same scenario will save less. The operating characteristic of a 30mA device is designed to be just on the survivable side of the current vs.

What is a 100mA RCD used for?

‘High sensitivity’ RCDs, rated 30mA or even 10mA, are designed to disconnect the supply within 40ms at 150mA and within 300ms at rated tripping current to protect the user. ‘Medium sensitivity’ devices, rated 100mA or more will provide protection against fire risks but will not provide full personal protection.

What mA should a 30mA RCD trip at?

For example, a 30mA RCD may trip at currents of around 18mA to 22mA.

What is the maximum tripping time for a 100mA RCD?

In the current Regulations, the maximum time allowed is 1s, in the 16th the time was 5s. The tripping current should be no greater than 5x the rated operating current. As such a 100mA RCD should trip within 1s (5s for 16th) at a test current no greater than 500mA.

Why are RCDs set at 30 mA?



To prevent electrocution, RCDs should operate within 25–40 milliseconds with any leakage currents (through a person) of greater than 30 mA, before electric shock can drive the heart into ventricular fibrillation, the most common cause of death through electric shock.

What is the tripping time for a 300mA RCD?

Is it a new RCD or an old RCD – ie to BS EN 61008 or to BS 4293. If the latter the time should be 200mS at 1 x tripping current. The 5 x test is only required if the RCD is providing supplementary protection.



See Also:

Technical discussion forums
· Other and general engineering discussions
Archived categories