According to the diagram on the labels inside the cabinet proper, the furthest-right screw position on the neutral intertie bar is where the bonding screw goes, and it appears to be already populated in your photos, as it should be.

Where do you put a bonding screw?

Quote from the video:
Quote from Youtube video: It will be located here on the neutral bar and in the home line load centers it will be located here above the neutral bar.

What is a bonding screw for in a service panel?





Quote from the video:
Quote from Youtube video: The bonding screw is that green headed screw right there. So that screw just simply threads through the neutral bus.

How do you bond an electrical panel?

Quote from the video:
Quote from Youtube video: Then we would run bonding jumpers between each one of them so that now they're all connected in some meaningful. Way that's really it that's a difference between grounding and bonding.

Where does the green bonding screw go?

For a single family house, many times the load center is the main panel, with the main breaker acting as the Service disconnect. In this panel, the green screw is used to bond (fasten) the neutral to the metal box. This is only done in the main panel.

Do you bond a main panel?

The reason we sometimes bond the neutral and ground wire in the main panel is for cost savings. There is no electrical engineering advantage in this bond; it is there because it is often cheaper to install a jumper wire than it is to route a ground wire all the way from the transformer to the panel.

What is a bonded electrical panel?





Electrical bonding is the practice of intentionally electrically connecting all exposed metal items not designed to carry electricity in a room or building as protection from electric shock.

Where do you bond neutral and ground?

Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are “bonded” to earth ground at either the electrical service entrance, or at transformers within the system.

Should a sub panel be bonded?

Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

How do you ground a service panel?

How to Run a Ground Wire to an Electrical Panel in 10 Minutes

  1. Ground bar or rod Installation.
  2. Attach your ground wire to the ground rod.
  3. Keep the breakers off.
  4. Remove panel cover.
  5. Pick a proper knock-out hole.
  6. Locate neutral bar or grounding bar.
  7. Connect the ground wire to the bar or rod.
  8. Finish up.



Can neutral and ground go on same bar?

The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

How do you install a ground bar on a panel?

Loosen a ground wire screw on either end of your ground bar. Slide your main ground wire, the one from your grounding rod, through the hole on the side of ground bar at the screw you loosened. Strip the end if necessary with wire strippers. Tighten the screw back into place firmly.

Can I tie the neutral and ground together?



No, the neutral and ground should never be wired together. This is wrong, and potentially dangerous. When you plug in something in the outlet, the neutral will be live, as it closes the circuit. If the ground is wired to the neutral, the ground of the applicance will also be live.

Can neutral and ground be tied together?

No, the neutral and ground should never be wired together. This is wrong, and potentially dangerous. When you plug in something in the outlet, the neutral will be live, as it closes the circuit. If the ground is wired to the neutral, the ground of the applicance will also be live.

Do I have to bond a sub panel?

Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

What kind of screw can I use for grounding?

Ground screws must be -32 thread pitch or finer, and must be threaded into the metal box. 10-32 is the “conventional” size. And most metal boxes have a hole tapped for a #10-32 screw for precisely that purpose. This is visible as a hole slightly smaller than the normal mounting holes.

Are neutral and ground wires together in a main panel?



At the main service panel, the neutral and grounding wires connect together and to a grounding electrode, such as a metal ground rod, which is there to handle unusual pulses of energy, such as a lightning strike. This is the only point at which the neutral connects to ground.

Where do you bond ground and neutral?

Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are “bonded” to earth ground at either the electrical service entrance, or at transformers within the system.

Do you bond neutral and ground in SubPanel?

When Should Grounds & Neutrals Be Connected in a SubPanel? The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.

Can you touch neutral bar in panel?

You can touch a neutral bus bar assuming the circuit is correctly grounded. The reason this is possible comes down to the amount of voltage in a current. The current passing through to a neutral bus bar will already have been used by the load.

Is the neutral bar and ground bar the same?



At the service panel (ONLY AT THE SERVICE PANEL – HUGELY IMPORTANT) the neutral bus bar is bonded to ground. You should see the ground lead and neutral tied to the same bus (the neutral bus bar). Based on your description, it sounds like your panels are wired correctly.

Can you get a shock off a neutral bar?

So even the current returns through neutral (only from a connected load that completes the current flow circuit) you touching the neutral with a 0V cant get you a shock. But its not safe to touch neutral wire!

Does the neutral bar carry current?

It is important to note that a neutral bar does still carry current even if the voltage at the location of the neutral bar is essentially zero with respect to ground. All of the current used in appliances all over the building goes through the neutral bar and back to the current source, the utility line.

Can I touch neutral wire?

If you touch the neutral wire in a live circuit, whether it be a lamp, an appliance or something else, it is the same as touching the active wire. It is only “safe” to touch the neutral wire when there is no current flowing, just as it is “safe” to touch the earth wire (when one exists).

What happens when you touch hot to neutral?

Every electrical device requires the electricity to do work, and that work involves electrical resistance, which limits the current flow. But if the hot wire touches the the neutral wire without passing through a load, the resistance suddenly becomes very low, and that makes the current flow very high.