It is perfectly fine and within code. The only stipulations are that you must splice the neutral, you cannot use the screws on one device to carry the neutral to the other, and that you must use a two-pole or handle-tied breaker.

Can 2 electrical circuits share a neutral?

What is a multiwire branch circuit? A multiwire branch circuit is a branch circuit with a shared neutral. This means there are two or more ungrounded (hot) phase or system conductors with a voltage between them and a shared neutral.

Can you tie neutrals together from different circuits?





Tying neutrals of different circuits together is effectively paralleling wire, which unless larger than 1/0 is also a violation of 310.4. 300.3 references 310.4, tho 300.3 says all conductors of a circuit must be in the same cable, raceway, etc unless allowed elsewhere.

Can neutral be common?

A neutral wire is any wire with 0 volts potential to ground, hence a neutral potential. A common is generally a hot, which is common to multiple points in the circuit, the neutral is your return to source completing the circuit. But in a network set up (2 hot’s sharing a neutral) the neutral is common.

How many branch circuits can share a neutral?

As you also mention, neutral conductors are not allowed for more than one branch circuit or one multiwire branch circuit or one set of ungrounded feeder conductors as stated in 200.4(A), unless specifically permitted elsewhere in this Code.

What happens when two neutrals touch?

If two neutrals are under one lug and you only switch off one circuit breaker the second circuits return path will remain energized causing a dangerous hazard if contact is made by the electrician or arcing if the neutral wire comes in contact with any grounded parts of the panel.

Can you daisy chain neutral?





Yes, you can and it will work. Ultimately this is your home, you know the reccemended way is to join them all up at the same point and not jump from switch to switch.

Can multiple switches use the same neutral wire?

If both switches are powered by the same breaker you can wire both to the same neutral.

Can you put 2 neutral wires together in a breaker box?

Bottom Line. Many homes have neutral bars that have too many neutral wires in one hole or slot. Generally this does not create a problem for the homeowner, however, it is an easy fix and most home inspectors recommend correcting the issue.

Can 2 circuits share a ground?

The code requires each branch circuit to have an equipment ground (either a wire, or conduit, or cable tray as in 250.120A), they can be shared when they are in the same raceway. If all the 20A circuits are in one raceway then you just need one ground.

How many hot wires can share a neutral?



two hot wires

(Basically, two hot wires are sharing a neutral wire.)

Can two different circuits share a box?

The answer is yes you can have 2 separate circuits in the same box (they can have a splice also but not needed in your case). The only concern would be the total box fill. Based on the NEC the wire fill would be calculated at 2.0 for each conductor for 14 gauge wire and 2.25 for 12 gauge wire.

How do you wire a neutral shared circuit?




Quote from Youtube video: And the other goes to a switched outlet controlled by the other pair of 3-way switches bottom Center is two black wire splice together that's just the in and out for the circuit connected to breaker.

What is a borrowed neutral?

A borrowed neutral is when you have two seperate circuits but you have taken the neutral from one circuit to supply the other with a neutral.

Does NEC allow shared neutrals?

Sharing neutral or yoke



The NEC does not define multiple circuits. However, relating to 210.7, it appears to mean more than one circuit, on separate phases and each with its own neutral. If the circuits were on the same phase, simultaneous disconnection in the panelboard would not be possible.

What is a common neutral?

A shared neutral is a connection in which a plurality of circuits use the same neutral connection. This is also known as a common neutral, and the circuits and neutral together are sometimes referred to as an Edison circuit.

Can arc fault breakers share a neutral?



Can the AFCI with shared neutral be used for retrofit installations? Yes, for retrofit installation, GE AFCIs can be substituted for the existing thermal magnetic breakers without the need to sort out existing shared or mixed neutrals.

Is common neutral or live?

The faceplate of a single, one-way switch has two terminals: “L1” is the terminal to which the neutral core wire is attached – the blue wire (traditionally black, before the change). “COM” or “Common” is the terminal to which the live core wire is attached – this is the brown wire (formerly red).