No, you should never connect ground and neutral together. There is only one place where the two are joined together and that is inside the primary power panel at the service entrance.

Should neutral and ground be bonded in main panel?

A high-resistance reading (typically greater than 200 ohms) indicates that there are no metallic paths between the panel and the transformer, and therefore a neutral-to-ground bond in a grounded system is required.

Are neutral and ground bonded?





Neutral wires are usually connected at a neutral bus within panelboards or switchboards, and are “bonded” to earth ground at either the electrical service entrance, or at transformers within the system.

Do you have to bond neutral and ground on SubPanel?

Here it is: Your ground and neutral wires definitely need to bond (or connect) together. But this is ONLY allowed in the main panel— never a subpanel, or anywhere else in the home. This is a very common mistake we see in the electrical part of your inspection.

What happens if the neutral isn’t bonded at the panel?

If the ground is not bonded to neutral, then the entire ground circuit in the building becomes close to hot until the circuit breaker trips. Ground rods can have several ohms of resistance to ground, which is far too high to keep the ground to safe Voltage in such a situation.

Should subpanel be bonded?

Rule #3: In a subpanel, the terminal bar for the equipment ground (commonly known as a ground bus) should be bonded (electrically connected) to the enclosure. The reason for this rule is to provide a path to the service panel and the transformer in case of a ground fault to the subpanel enclosure.

Should main panel be bonded?





You are correct–the panel should not be bonded. Most panels will come with a bonding screw in case it is being used as a main panel and first means of disconnect, which yours isn’t.

How do you know if neutral is bonded to ground?

The neutral and ground do not appear to be bonded. On the right, it appears there’s a green screw. According to the drawing, this makes sense, as it serves to bond the enclosure to the ground. It’s marked on the drawings as “Bonded.” It likely came from the factory like this.

Why do you tie the neutral and ground together?

People rely on the ground to defend against deadly shocks because it offers the path of least resistance. Therefore, if you connect the neutral to the ground, most current passes through the ground. This makes an electric shock more likely, especially if the connected appliance is defective.

Should neutral be grounded?

The neutral (connected to the center tap in the main panel) can and does carry an electrical charge, so the neutral bus bar should be grounded to the outside through the use of a grounding rod to bring Neutral to Earth Ground.

Should neutral-to-ground have voltage?



Some neutral-to-ground voltage should be present under load conditions, typically 2V or less. If the voltage is zero with a load on the circuit, then check for a neutral-to-ground connection in the receptacle, whether accidental or intentional.

Why is the ground and neutral isolated in a subpanel?

Grounds and neutrals were isolated to provide separate paths back to the panel. Another way to wire a subpanel was with a three-wire feed; two hots and a neutral, with grounds and neutrals connected together at the subpanel.

What is the difference between a ground and a neutral?

While a ground wire and neutral wire are connected, they serve different functions in the overall electrical scheme. The neutral wire is part of the normal flow of current, while the ground wire is a safety measure in case the hot wire comes in contact with the metal casing of an appliance or other shock hazard.

What is the difference between neutral bar and ground bar?



Neutral bars have a heavy, high-current path between the bar and neutral lug, which is itself isolated from the chassis It is obvious that the neutral lug-to-bar connection is heavy, and designed to flow a lot of current all the time. Ground bars are, by design, in direct contact with the panel chassis.

Why is there no ground bar in my panel?

You don’t have a ground bus because you don’t need one. All existing wiring is in metal conduit, which provides the ground. If you are in a location where local electrical code requires metal conduit, then by definition all your new circuits will have metal conduit as the ground path.

Can you add a neutral bar to a panel?

You CANNOT add a neutral bus.

So the neutral bars have thermal considerations ground bars do not, as well as, you don’t want current to normally be present on the panel chassis, which is grounded. So you cannot add additional neutral bars, but they provided enough neutral slots for your needs, so you are all set.

Do I need a ground rod for my sub panel?



Yes, any sub panel outside of the main building requires it’s own ground rod and a ground wire back to the main building. And yes, a sub panel in the same building as the main does not need a ground rod – only the ground wire.

How far can a ground rod be from panel?

NEC Article 250 does not specify a minimum or maximum distance between the main electrical panel and the ground rod. Because the panel must be connected to the ground rod by a buried copper wire, however, best practices suggest that the shorter the distance to the ground rod, the more efficient the ground.

Why are 2 ground rods required?

If it has a ground resistance of 25 ohms or more, 250.56 of the 2005 NEC requires you to drive a second rod. But many contractors don’t bother measuring the ground resistance. They simply plan on driving two rods because doing so will meet the requirements of 250.56, regardless of actual ground resistance.